Chromalox V-2030 Identifikasi Suku Cadang Instalasi dan Pembaruan - Halaman 2
Jelajahi secara online atau unduh pdf Identifikasi Suku Cadang Instalasi dan Pembaruan untuk Pemanas Chromalox V-2030. Chromalox V-2030 2 halaman. Industrial wall mounted convection space heater
Juga untuk Chromalox V-2030: Identifikasi Suku Cadang Instalasi dan Pembaruan (2 halaman)
Width
Height
WARNING: Hazard of Shock. Any installation involving
electric heaters must be effectively grounded in accor-
dance with the National Electrical Code to eliminate
shock hazard.
Note: All wiring should be done in accordance with local codes and the
L1
Line 240V
L2
Figure 1 — 240 Volt Heaters
WARNING: Hazard of fire or discoloration of temperature
sensitive fabrics. Keep combustible materials and such
fabrics at least 4" away from front of cover or above cover.
DANGER:Hazard of Fire. This heater is not intended for
1. WARNING: Hazard of Shock. Disconnect all power
before attempting to service this heater.
2. Following long periods of idleness, heater should be vacuumed
before start-up to remove accumulated combustible particles which
will incinerate causing smoking and consequent wall discoloration.
MOUNTING
5-3/4
3/4
RENEWAL PARTS IDENTIFICATION
Model
V-2020
V-2030
V-2030
V-2040
V-2040
4 or 6 Elements
OPERATION
MAINTENANCE
Limited Warranty:
Please refer to the Chromalox limited warranty applicable to this product at
http://www.chromalox.com/customer-service/policies/termsofsale.aspx.
2150 N. RULON WHITE BLVD., OGDEN, UT 84404
Phone: 1-800-368-2493
Heater Mounting —
Model
V-2020
V-2030
V-2040
WIRING
National Electrical Code by a qualified person as defined in the NEC.
1. Electrical wiring enters heater case through 7/8" opening in end of
heater.
2. Grounding conductor, with green insulation, should be secured to
grounding screw located on case.
1
Heating Element
Type V
(Iron Sheath)
Volts Watts
(Prefix 152-)
240
2000
SE-2450 240V 500W (4)
108259-001
240
3000
SE-2475 240V 750W (4)
108259-001
480
3000
SE-2475 240V 750W (4)
108259-001
240
4500
SE-2475 240V 750W (6)
108259-002
480
4500
SE-2475 240V 750W (6)
108259-002
L1
Line 480V
L2
use in hazardous atmospheres where flammable vapors,
gases, liquids or other combustible atmospheres are pre-
sent as defined in the National Electrical Code. Failure to
comply can result in explosion or fire.
3. If heater is located in areas of heavy traffic, furnish suitable heater
guard (wall mounted pipe rail in front of case, for example) to pre-
vent damage to heater.
www.chromalox.com
Dimensions (In.)
Height
Width
Depth
27
12-3/4
27
12-3/4
27
17-3/4
2
3
4
Heater
Insulating
Insulating
Cover
Bushing
Bushing
(Prefix 032-)
(Prefix 032-)
010978-001 (8)
010978-002 (8)
010978-001 (8)
010978-002 (8)
010978-001 (8)
010978-002 (8)
010978-001 (12) 010978-002 (12)
010978-001 (12) 010978-002 (12)
4 or 6 Elements
Figure 2 — 480 Volt Heaters
5-3/4
5-3/4
5-3/4
Wire
Wiring
Sizes
Diagram
(90˚C Min)
Fig No.
#16
1
#16
1
#16
2
#14
1
#16
2