B. HEAT PUMP PLACEMENT & CLEARANCES
WATER IN/OUT PORT INDI-
CATOR LABEL
1. To allow for proper condensation drainage,
use a level slab to elevate the heat pump to
at least the same height as the pool filter
system slab, or 2 to 3 inches minimum
above grade.
2. Allow the minimum air flow clearances on
top and the sides as shown here. Make sure
the unit can "breathe" well. Do not install
indoors or where the discharge air can ac-
cumulate and be drawn back through the
heater. Make sure the front is accessible
for future service.
3. Keep sprinkler heads at least 6 feet away
from the heat pump. Do not allow the
sprinkler to spray the unit in any way to
prevent damage.
4. If the unit is installed under a roof overhang
or under a roof valley, a gutter or diverter
should be fitted to prevent excessive water
from pouring through the unit.
5. Keep all plants and shrubs trimmed away
from the heater to the minimum clearances
shown here to prevent air coil damage.
6. If the heater is installed above or below
the pool water level by more than 3 feet
you may require an external water flow
switch. See the bottom of page 7 for more
information.
Titanium Instal Manuals.indd 4
FAN DISCHARGE
AIR FLOW OUT
AIR COIL
AIR FLOW IN
S
ON 3 SIDE
2" THREADED MALE
PIPING CONNECTIONS
Minimum Air Flow
& Access
Clearances
BACK
AIR
9"
COIL
TOP
12"
12"
FRONT
36"
48"
6 FT
2"
-4-
ELECTRICAL CONNECTIONS AND WIRING
5. INTERFACING DIGITAL LOGIC CONTROL MODELS
with Jandy™Aqualink RS & Compool
To interface the "Digital Logic" digital control heat pump models with the Jandy AquaLink RS series
or Compool, run a 2 wire (16 A.W.G. or larger) insulated cable from the device to the heat pump.
Remove the 6 screws from the heaters front service access panel and open. Look for the heaterʼs
solid state circuit board located inside the top portion of the electrical compartment mounted on the
rear wall. Locate, remove and discard the "METAL JUMPER TAB" attached to the bottom terminal
bar and labeled "Jandy/Compool". Then, run a 2 wire cable from the 2 position terminal where the
metal jumper tab was, through the heaterʼs low voltage access port, then to the AquaLink RS or the
Compool control.
NOTE for AquaLink RS and Compool: Turn both heater thermostats all the way up and set the
mode selector switch to pool and do not use the heater controls as the Jandy or Compool now has
thermostatic control over the heater.
for AquaLink
Attach the 2
wire cable to
positions #1
and position
# 2 on the 10
slot, green ter-
minal bar inside
the AquaLink's
power center.
*See the con-
trollers instal-
l a t i o n g u i d e
also.
FOR AQUALINK/COMPOOL
REMOVE METAL JUMPER
GREEN TERMINAL BAR
POSITIONS 1 & 2
JANDY AQUALINK PC BOARD
-13-
for Compool
Attach the 2
JUMPERS
wire cable to