Battery
Battery level shows current value, battery frame
Overheating
blink, fault icon blink
Load failure
Load overload
When load current reaches1.02-1.05 times 1.05-1.25 times, 1.25-1.35 times and
1.35-1.5 times more than nominal value, controller will automatically turn off loads in 50s,
30s,10s and 2s respectively
4.3 Load mode setting
Operating Steps:
Under load mode setting interface, press SET button and hold on 5s till the number begin
flashing, then press MENU button to set the parameter, press SET button to confirm.
Timer 1
Light ON/OFF
Load will be on for 1 hour
since sunset
Load will be on for 2 hours
since sunset
Load will be on for 3~13
hours since sunset
Load will be on for 14 hours
since sunset
Load will be on for 15 hours
since sunset
Test mode
Manual mode(Default load
ON)
NOTE: Please set Light ON/OFF, Test mode and Manual mode via Timer1. Timer2
will be disabled and display "2 n".
4.4 Battery Type
 Operating Steps
Under Battery Voltage interface, press SET button and hold on 5s then enter into the
interface of Battery type setting. After choosing the battery type by pressing MENU button,
waiting for 5s or pressing SET button again to modify successfully.
 Battery Type
①Sealed (Default)
NOTE: Please refer to the battery voltage parameters table for the different battery
type.
5. Protections
Protection
Conditions
PV Reverse
When the battery is correct connecting, the
Polarity
PV can be reversed.
Battery Reverse
When the PV is not connecting, the battery
Polarity
can be reversed.
Battery Over
The battery voltage reaches to the OVD
Voltage
Battery Over
The battery voltage reaches to the LVD
Discharge
Temperature sensor is higher than 65℃
Battery
Overheating
Temperature sensor is less than 55℃
7.Technical Specifications
Item
VS1024AU
Nominal system voltage
Battery input voltage range
Rated charge/discharge current
10A@55℃
Max. PV open circuit voltage
Battery type
Equalize Charging Voltage
Boost Charging Voltage
Float Charging Voltage
Low Voltage Reconnect
Voltage
Low Voltage Disconnect
Voltage
Self-consumption
Temperature compensation
coefficient
Charge circuit voltage drop
Discharge circuit voltage drop
LCD temperature range
Working environment
temperature
Relative humidity
Enclosure
Grounding
USB output
Overall dimension
142x85x41.5mm 160x94.9x49.3mm
Mounting dimension
130x60mm
Mounting hole size
Terminals
4mm
Net weight
※Above the parameters are in 12V system at 25℃, twice in 24Vsystem, triple in 36V system and quadruple in 48V system.
,Load short circuit
Timer 2
Disabled
Load will be on for 1 hour
before sunrise
Load will be on for 2 hours
before sunrise
Load will be on for 3~13
hours before sunrise
Load will be on for 14
hours before sunrise
Load will be on for 15
hours before sunrise
Disabled
Disabled
②Gel
③Flooded
The controller is not
damage
Stop charging
Stop discharging
Output is OFF
Output is ON
VS2024AU
VS3024AU
12/24VDC
Auto
9V~32V
20A@55℃
50V
148x70mm
Φ4.5mm
2
2
/12AWG
10mm
/8AWG
0.22kg
0.35kg
3
Controller
Overheating
Load Short
Circuit
Load Overload
Damaged RTS
6. Troubleshooting
Faults
The
LCD
during daytime when
sunshine falls on PV
modules properly
Wire connection is
correct,
LCD
display
8. Disclaimer
Status
This warranty does not apply under the following conditions:
1) Damage from improper use or use in an unsuitable environment.
2) PV or load current, voltage or power exceeding the rated value of controller.
3) The controller is working temperature exceed the limit working environment
temperature.
4) User disassembly or attempted repair the controller without permission.
5) The controller is damaged due to natural elements such as lighting.
6) The controller is damaged during transportation and shipment.
VS3048AU
12/24/36/48VDC
Auto
9V~64V
30A@55℃
96V
Sealed(Default) / Gel / Flooded
Sealed:14.6V/ Gel: No/ Flooded:14.8V
Sealed:14.4V/ Gel:14.2V/ Flooded:14.6V
Sealed/Gel/Flooded:13.8V
Sealed/Gel/Flooded:12.6V
Sealed/Gel/Flooded:11.1V
≤9.2mA/12V;≤11.7mA/24V; ≤14.5mA/36V;≤17mA/48V
-3mV/℃/2V(25℃)
≤0.29V
≤0.16V
-20℃~+70℃
-25℃~+55℃(Product can work continuously at full load)
≤95%, N.C.
IP30
Common Positive
5VDC/2.4A(Total)
181x100.9x59.8mm
172x80mm
Φ5mm
2
16mm
/6AWG
0.55kg
0.58kg
Temperature sensor is higher than 85℃
Temperature sensor is less than 75℃
Load current ≥2.5 times rated current
One short circuit, the output is OFF 5s;
Two short circuit, the output is OFF 10s;
Three short circuit, the output is OFF 15s;
Four short circuit, the output is OFF 20s;
Five short circuit, the output is OFF 25s;
Six short circuit, the output is OFF
Load current ≥2.5 times rated current
1.02-1.05 times, 50s,
1.05-1.25 times, 30s
1.25-1.35 times,10s
1.35-1.5 times 2s
The RTS is short-circuited or damaged
Possible reasons
is
off
PV
array
disconnection
1) Battery voltage is
lower than 9V
2) PV voltage is less
not
than battery voltage
Interface
Battery over voltage
blink
Interface
Battery
blink
over discharged
Interface
Battery Overheating
blink
Interface
Over load or Short
blink
circuit
VS4524AU
VS4548AU
12/24VDC
12/24/36/48VDC
Auto
Auto
9V~32V
9V~64V
45A@55℃
50V
96V
194x118.4x63.8mm
185x90mm
Φ5mm
2
16mm
/6AWG
0.76kg
0.88kg
Any changes without prior notice!
4
Output is OFF
Output is ON
Output is OFF
Clear the fault:
Restart the controller
or wait for one
night-day cycle
(night time>3 hours).
Output is OFF
Clear the fault:
Restart the controller
or wait for one
night-day cycle
(night time>3 hours).
Charging or
discharging at 25℃
Troubleshooting
Confirm that PV wire connections
are correct and tight
1) Please check the voltage of
battery. At least 9V voltage to
activate the controller
2) Check the PV input voltage
which should be higher than
battery's
Check if the battery voltage is
higher than OVD point (over
voltage disconnect voltage), and
disconnect the PV.
When the
battery
voltage
is
restored to or above LVR point
(low voltage reconnect voltage),
the load will recover
The controller will automatically
turn the system off. But while the
temperature decline to be below
50 ºC, the controller will resume.
Please reduce the number of
electric
equipments
or
check
carefully loads connection.
VS6024AU
VS6048AU
12/24VDC
12/24/36/48VDC
Auto
Auto
9V~32V
9V~64V
60A@55℃
50V
96V
214x128.7x72.2mm
205x100mm
Φ5mm
2
25mm
/4AWG
1.02kg
1.04kg
Version
number:V1.2