Accurex Vari-Flow Panduan Pemasangan, Pengoperasian, dan Pemeliharaan - Halaman 12
Jelajahi secara online atau unduh pdf Panduan Pemasangan, Pengoperasian, dan Pemeliharaan untuk Kipas angin Accurex Vari-Flow. Accurex Vari-Flow 16 halaman. Air management system
Exhaust -
continued
EF Max Fan Speed Descriptors/Value Default Use
EF1 Max
EF2 Max
EF3 Max
EF4 Max
EF5 Max
Exhaust Temperature Set Points*
EF1 Low Temp
EF1 High Temp
EF2 Low Temp
EF2 High Temp
EF3 Low Temp
EF3 High Temp
EF4 Low Temp
EF4 High Temp
EF5 Low Temp
EF5 High Temp
Exhaust Mode
Exhaust in Fire
Fans Full Speed
100% Timer
Time Left
Exhaust Fans*
Fan1 Connected
Fan2 Connected
Fan3 Connected
Fan4 Connected
Fan5 Connected
Grease Grabber H2O with Vari-Flow Settings
GGH2O/
Vari-Flow Settings
GGH2O Force Fan Off No / Yes
GGH2O Fan Dry
Active
GGH2O Fan Mode
* To see values, you need to log in.
12
Vari-Flow Air Management System
0-100%
100%
0-100%
100%
0-100%
100%
0-100%
100%
0-100%
100%
°F
90°F
°F
115°F
°F
90°F
°F
115°F
°F
90°F
°F
115°F
°F
90°F
°F
115°F
°F
90°F
°F
115°F
No / Yes
Yes
No / Yes
-
Minutes
15 min
Minutes
-
No / Yes
Yes
No / Yes
No
No / Yes
No
No / Yes
No
No / Yes
No
Descriptors/Value Default Use
No
No / Yes
No
0-10 VDC
-
0-10 VDC
-
0-10 VDC
-
Indicates the maximum fan speed to meet design
airflow requirements for EF1
Indicates the maximum fan speed to meet design
airflow requirements for EF2
Indicates the maximum fan speed to meet design
airflow requirements for EF3
Indicates the maximum fan speed to meet design
airflow requirements for EF4
Indicates the maximum fan speed to meet design
airflow requirements for EF5
The temperature at which EF1 runs at the minimum speed.
The temperature at which EF1 runs at the maximum speed.
The temperature at which EF2 runs at the minimum speed.
The temperature at which EF2 runs at the maximum speed.
The temperature at which EF3 runs at the minimum speed.
The temperature at which EF3 runs at the maximum speed.
The temperature at which EF4 runs at the minimum speed.
The temperature at which EF4 runs at the maximum speed.
The temperature at which EF5 runs at the minimum speed.
The temperature at which EF5 runs at the maximum speed.
Indicates the exhaust fan(s) will run in case of fire
Indicates the operator overrode the exhaust fan to full
speed operation
The set time the fan 100% override runs for.
Indicates the time remaining for the full speed
override
Indicates if EF1 is connected
Indicates if EF2 is connected
Indicates if EF3 is connected
Indicates if EF4 is connected
Indicates if EF5 is connected
If yes the exhaust fan(s) are forced off to prevent
water from being drawn into the exhaust duct during
the wash cycle. The fan button on the keypad is
disabled.
If yes, the exhaust fan(s) is(are) forced on to dry the
filters following the wash cycle.
0 V-Fan(s) Auto
5 V-Fan(s) Off
10 V-Fan(s) Dry