3. Check the Operating System version
·
To avoid problems with different OS versions in the Pluto
system, it is a good idea to check that the correct version
of the OS is downloaded to all Pluto units. The most
convenient way to do this is with "OnlineInfo →Pluto
connected to PC" under the "Tools" menu.
The latest version of OS can be obtained by contacting
Jokab support.
4. Check that Er20 is shown in the Pluto display window
·
If another fault code is shown in the display window; the program shall be erased from the unit,
resulting in Er20 shown on the display. If another fault code is shown, the Pluto can be restarted with
voltage off/on or with the command "Reset all Pluto's" under the "Tools" menu.
·
Repeat the procedure for all units in the system.
5. Download the program
·
Compile and download the project file in one of the Pluto units. Check that all units have the program
downloaded in the window that is shown. Pay attention to the units that eventually have not been
correctly loaded. Select "Start PLC program".
·
Fault code Er26 is going to be shown in the Pluto display. This is normal and is acknowledged with
the "Reset all Pluto's" command under the "Tools" menu or with voltage off/on at all units.
·
Check the system with the "Bus Status" command under the "Tools" menu. All units shall be
green/OK. If there are fault codes, check in the manual and perform necessary measures.
2
or your local ABB
2TLC172007M0203_B.doc