Accutrol T-ABVA Panduan Pemasangan, Pengoperasian & Pemeliharaan - Halaman 7

Jelajahi secara online atau unduh pdf Panduan Pemasangan, Pengoperasian & Pemeliharaan untuk Sistem Kontrol Accutrol T-ABVA. Accutrol T-ABVA 16 halaman.

Specifications

INPUT POWER
15VDC +/- 20% provided by Class II UL approved wall pluggable power module
VELOCITY RANGE
30 – 2,000 FPM
ACCURACY
+/- 10% of set point or +/- 10 FPM, whichever is greater
VELOCITY SENSOR
Type: micro-bridge mass flow sensor
Overpressure: 25 PSI
ENVIRONMENT
Temperature: Storage; 0°F to 150°F, Nominal Operating; 55°F to 85°F
Humidity: 10% to 90% RH, non-condensing
PHYSICAL CHARACTERISTICS
Enclosure Size: 2.76" W x 4.5"H x 1.25"D
Weight: approximately 5oz.
Hood Probe: 7/16" diameter, feed through bushing, press fit, 5' tubing
Materials: Enclosure; ABS plastic
Tubing; 0.170" I.D., ¼" O.D., clear polyurethane, ester base
Hood Probe; Polyethylene
LED INDICATORS
Two ultra bright clear lens LEDs, Green indicates normal, Red flashing indicates alarm
AUDIBLE HORN
Sound Level: 90 dB at 10cm
Operation: horn sounds during alarm condition unless Mute is activated
Re-Beep Mode: single fast tone every 5 minutes when horn muted and alarm not cleared.
ALARM DELAY
7 seconds (to reduce false alarms)
ALARM RELAY OUTPUT (I/O Terminal, Positions 3, 4 and 5)
Type: SPDT relay
Specifications: 1A @ 30 VDC, 0.5A @ 125 VAC (resistive load)
Operation:
Relay Contact Term. 3 – 4:
Relay Contact Term. 5 – 4:
REMOTE MUTE INPUT (I/O Terminal, Positions 1 and 2)
Type: un-powered dry contact
Operation: when input is shorted (1000 ohms max), horn is muted and re-beep mode active
MUTE PUSH BUTTON
Pressing Once Momentarily silences horn, enables re-beep mode and resets after the alarm
condition is cleared or the Mute Button is pressed momentarily again.
Pressing and Holding Mute for 3 Seconds provides indication of present calibration mode.
One LED ON indicates Cal Mode 1, Both LEDs ON indicates Cal Mode 2.
Pressing and Holding Mute for 15 Seconds while in alarm disables the horn with re-beep
inactive. If alarm clears, or mute is pressed for 15 seconds, normal operation is restored.
T-ABVA Manual |Rev.C, JULY 2017
NORMAL, Power ON
OPEN
CLOSED
ALARM, Fault or Power Loss
CLOSED
OPEN
Page 3