Hazardous Voltage.
Hazardous Voltage.
Will cause death or serious injury.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before
Turn off and lock out all power supplying this device before
working on this device.
working on this device.
Replace all covers before power supplying this device is
Replace all covers before power supplying this device is
turned on.
turned on.
3
Wire Connector
[ Conexión
del cable ]
8 mm
OR
5/16"
TAW1FG350 / 3VL9335-4TD01
3TAW1FG350 / 3VL9335-4TD31
4TAW1FG350 / 3VL9335-4TD41
8 mm
OR
5/16"
TCW1FG350 / 3VL9335-4TD11
3TCWFG350 / 3VL9335-4TD61
GWA 4NEB 179 6872-10 DS 04
Order No. / Referencia: 3ZX1012-0VL68-5AA2
Tensión peligrosa.
Tensión peligrosa.
Puede causar la muerte o lesiones graves.
Puede causar la muerte o lesiones graves.
Desenergice totalmente antes de instalar o darle servicio.
Desenergice totalmente antes de instalar o darle servicio.
Reemplace todas las barreras y cubiertas antes de
Reemplace todas las barreras y cubiertas antes de
energizar el interruptor.
energizar el interruptor.
A
Wire Size
[ Rango Cable ]
CU / AL
Class B
Cu / Al
7 STRANDS
4 AWG
Cu / Al
3 – 1 AWG
7 STRANDS
[ 25 - 35 mm² ]
Cu / Al
19 STRANDS
1/0 – 4/0 AWG
[ 70 – 95 mm² ]
250 - 350 kcmil
37 STRANDS
[ 120 - 150 mm
]
2
Cu Only
7 STRANDS
4 AWG
Cu Only
3 – 1 AWG
7 STRANDS
[ 25 - 35 mm² ]
Cu Only
19 STRANDS
1/0 – 4/0 AWG
[ 70 - 95 mm² ]
Cu Only
250 - 350 kcmil
37 STRANDS
[ 120 - 150 mm
]
2
UL 486A - 486B
Req. Wire Stranding
( Cable )
CU
Class C
19 STRANDS
19 STRANDS
37 STRANDS
61 STRANDS
19 STRANDS
19 STRANDS
37 STRANDS
61 STRANDS
Tension dangereuse.
Tension dangereuse.
Danger de mort ou risque de blessures graves.
Danger de mort ou risque de blessures graves.
Couper l'alimentation de l'appareil et barrer avant de
Couper l'alimentation de l'appareil et barrer avant de
travailler.
travailler.
Remplacez touts les couverts avant que
Remplacez touts les couverts avant que
l'approvisionnement de pouvoir soit alimenté.
l'approvisionnement de pouvoir soit alimenté.
Torque
[ esfuerzo de torsión ]
150 lb. in.
[ 17 Nm ]
200 lb. in.
[ 23 Nm ]
275 lb. in.
[ 31 Nm ]
150 lb. in.
[ 17 Nm ]
200 lb. in.
[ 23 Nm ]
275 lb. in.
[ 31 Nm ]
Wire
Strip
Length
[ Quitar ]
A
.87"
[ 22 mm ]
3