PROFIenergy
7.2 Response of the analog input module
Mode parameter
The following table shows the "Mode" parameter.
Table 7- 1
Element
Mode
Encoder supply U
1
deactivated in these measurement types.
44
Mode parameter
Code
0
: PE_MODE_PROCEED
D
1
: PE_MODE_SHUTDOWN
D
3
: PE_MODE_LAST_VALUE
D
4
: PE_MODE_SUBST_VALUE
D
is only provided for measurement type current and voltage and can only be
S
Explanation
Proceed at "pause"
Value status "GOOD"
Switch off at "pause"
Encoder supply U
Pause substitute value: 7FFF
Value status "BAD"
Last value at "pause"
Encoder supply U
Pause substitute value: Last input value
Value status "BAD"
Substitute value at "pause"
Encoder supply U
Pause substitute value: Configured pause
substitute value
Value status "BAD"
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)