Juga untuk Siemens simatic ET 200MP: Manual (40 halaman), Manual (24 halaman), Manual (29 halaman), Manual (47 halaman), Manual (26 halaman), Manual (28 halaman), Manual (50 halaman), Manual (34 halaman), Panduan Pengguna (44 halaman), Manual (30 halaman), Manual (25 halaman), Manual (28 halaman), Manual (33 halaman), Manual (49 halaman), Manual (36 halaman), Manual (39 halaman), Manual (28 halaman), Panduan Peralatan (35 halaman), Panduan Peralatan (32 halaman), Manual (29 halaman), Manual (34 halaman), Manual (36 halaman), Panduan Peralatan (50 halaman), Manual (45 halaman)

Siemens simatic ET 200MP Manual

Address space

4.1
Address space
The module can be configured in various ways in STEP 7. Depending on the configuration,
additional/different addresses are assigned in the process image input/output.
Configuration options of DI 16x24VDC/DQ 16x24VDC/0.5A BA
You can configure the module with STEP 7 (TIA Portal) or with a GSD file.
When you configure the module by means of the GSD file, the configurations are available
under different abbreviations/module names.
The following configurations are possible:
Table 4- 1
Configuration options
Configuration
1 x 32-channel without value status (1 x 16
digital inputs and 1 x 16 digital outputs)
4 x 8-channel without value status (2 x 8
digital inputs and 2 x 8 digital outputs)
1 x 32-channel with value status for up to 4
submodules
(each 1 x 16 channels for module-internal
Shared Input or Shared Output)
14
Short designation/
module name in the GSD
file
DI 16x24VDC/
DQ 16x24VDC/0.5 BA
DI 16x24VDC/
DQ 16x24VDC/0.5 BA S
DI 16x24VDC/
DQ 16x24VDC/0.5 BA MSI
or MSO
Digital input/output module DI 16x24VDC/DQ 16x24VDC/0.5A BA (6ES7523-1BL00-0AA0)
Configuration software, e.g., with STEP 7 (TIA
Portal)
Integrated in hardware
catalog
STEP 7 (TIA Portal)
V13 or higher
V13 Update 3 or higher
(PROFINET IO only)
V13 Update 3 or higher
(PROFINET IO only)
Manual, 09/2014, A5E32364588-AB
4
GSD file in STEP 7
(TIA Portal) V12 or
higher or STEP 7
V5.5 SP3 or higher
X
X
(PROFINET IO only)
X