Juga untuk Siemens SIMATIC ET 200S: Panduan Operator (18 halaman), Manual (16 halaman), Panduan Pengguna (16 halaman), Panduan Pengguna (26 halaman), Manual (37 halaman), Manual (24 halaman), Manual Fungsi (40 halaman), Petunjuk Pengoperasian (4 halaman), Petunjuk Pengoperasian Asli (19 halaman), Petunjuk Pengoperasian Asli (20 halaman), Manual (34 halaman), Manual (14 halaman), Manual (24 halaman), Petunjuk Pengoperasian Asli (17 halaman), Petunjuk Pengoperasian Asli (19 halaman), Manual (16 halaman), Manual (12 halaman), Manual (32 halaman), Manual (18 halaman), Manual (12 halaman), Manual (28 halaman), Manual (22 halaman), Manual (22 halaman), Manual (36 halaman), Manual (16 halaman)

Siemens SIMATIC ET 200S Manual
Diagnostics

3.2 Error types

3.2
Error types
Analog input module error types
Table 3-1
31
D
22
D
16
D
9
D
8
D
7
D
6
D
16
Error types
Error type
11111: Channel
The firmware is being updated.
temporarily
Channel 0 applies to the entire
unavailable
module. The module does not
perform any measurements
during this time.
10110: Hardware
A hardware interrupt was not
interrupt lost
detected.
10000: Parameter
Module cannot use the
assignment error
parameter for the channel:
Inserted module does not
match the configuration.
Faulty parameter assignment.
01001: Errors
Internal module error
(diagnostics message at
channel 0 applies to the entire
module)
01000: Lower value
Value is below the underrange. Correct the module/actuator
limit fallen below
00111: Violation of
Value is above the overrange.
higher limit
00110:
Line to the encoder
Open circuit
interrupted.
Meaning
2AI I 4WIRE HS analog electronic module (6ES7134-4GB62-0AB0)
Remedy
--
Correction or coordination of the
program, process, module
Correct the configuration (align
actual and set configuration).
Correct the parameter
assignment (diagnostics wire
break only for the allowed
measuring range
parameterized).
Replace the module.
tuning.
Correct the module/actuator
tuning.
Correct the process wiring.
Manual, 01/2008, A5E01076124-02