Juga untuk Siemens SIMATIC ET 200SP: Panduan Pengguna (21 halaman), Manual (34 halaman), Manual (48 halaman), Manual (30 halaman), Manual (34 halaman), Informasi Produk (38 halaman), Manual (37 halaman), Manual (36 halaman), Manual (44 halaman), Manual (31 halaman), Manual (35 halaman), Manual (23 halaman), Panduan Konfigurasi (20 halaman), Manual (34 halaman), Manual (29 halaman), Manual (33 halaman), Manual (31 halaman), Panduan Pengguna (32 halaman), Manual (31 halaman), Manual (28 halaman), Manual (41 halaman), Manual (32 halaman), Manual (49 halaman), Manual (24 halaman), Manual (34 halaman), Manual (41 halaman), Manual (30 halaman), Manual (31 halaman), Manual (27 halaman), Manual (24 halaman), Manual (24 halaman), Manual (25 halaman), Manual (49 halaman), Manual (40 halaman), Manual (38 halaman), Manual (39 halaman), Informasi Produk (24 halaman), Manual (32 halaman), Informasi Produk (10 halaman), Panduan Peralatan (43 halaman), Manual (33 halaman), Panduan Peralatan (44 halaman), Petunjuk Pengoperasian Asli (6 halaman), Manual (35 halaman), Manual (28 halaman), Panduan Peralatan (32 halaman), Manual (50 halaman), Manual (30 halaman), Manual (26 halaman), Manual (28 halaman), Manual (34 halaman), Manual (44 halaman), Manual (33 halaman), Panduan Peralatan (42 halaman), Manual Petunjuk Asli (16 halaman)

Siemens SIMATIC ET 200SP Manual
Product overview
2.6 Functions
Reference
You will find additional information on "PROFIBUS DP" in the STEP 7 online help and in the
PROFIBUS with STEP 7 (http://support.automation.siemens.com/WW/view/en/59193579)
function manual.
2.6.4

Memory reset

Apart from a few exceptions, a "memory reset" involves clearing all internal memories and
then reading in the data on the SIMATIC memory card.
Options
You have the following options for resetting the memory of the CPU:
● Using the mode selector
● Using STEP 7
Procedure using the mode selector
To perform a memory reset of the CPU using the mode selector, follow these steps:
1. Set the mode selector to STOP.
Result: The RUN/STOP LED lights up yellow.
2. Set the mode selector to the MRES position. Hold the switch in this position until the
RUN/STOP LED lights up yellow for the 2nd time and remains lit (this takes three
seconds). After this, release the switch.
3. Within the next three seconds, return the mode selector to the MRES position, and then
back to STOP.
Result: The CPU performs a memory reset. During the memory reset, the RUN/STOP LED
flashes yellow. The RUN/STOP LED lights yellow when the CPU has completed the memory
reset.
Procedure using STEP 7
To perform a memory reset of the CPU via STEP 7, follow these steps:
1. Open the "Online tools" task card of the CPU.
2. Click the "MRES" button in the "CPU operator panel" pane.
3. Click "OK" to confirm the security prompt.
Result: The CPU is in STOP mode and performs a memory reset.
18
CPU 1510SP F-1 PN (6ES7510-1SJ00-0AB0)
Manual, 12/2014, A5E35264953-AA