Juga untuk Siemens SIMATIC ET 200SP: Manual (40 halaman), Panduan Pengguna (21 halaman), Manual (34 halaman), Manual (30 halaman), Manual (34 halaman), Informasi Produk (38 halaman), Manual (37 halaman), Manual (36 halaman), Manual (44 halaman), Manual (31 halaman), Manual (35 halaman), Manual (23 halaman), Panduan Konfigurasi (20 halaman), Manual (34 halaman), Manual (29 halaman), Manual (33 halaman), Manual (31 halaman), Panduan Pengguna (32 halaman), Manual (31 halaman), Manual (28 halaman), Manual (41 halaman), Manual (32 halaman), Manual (49 halaman), Manual (24 halaman), Manual (34 halaman), Manual (41 halaman), Manual (30 halaman), Manual (31 halaman), Manual (27 halaman), Manual (24 halaman), Manual (24 halaman), Manual (25 halaman), Manual (49 halaman), Manual (40 halaman), Manual (38 halaman), Manual (39 halaman), Informasi Produk (24 halaman), Manual (32 halaman), Informasi Produk (10 halaman), Panduan Peralatan (43 halaman), Manual (33 halaman), Panduan Peralatan (44 halaman), Petunjuk Pengoperasian Asli (6 halaman), Manual (35 halaman), Manual (28 halaman), Panduan Peralatan (32 halaman), Manual (50 halaman), Manual (30 halaman), Manual (26 halaman), Manual (28 halaman), Manual (34 halaman), Manual (44 halaman), Manual (33 halaman), Panduan Peralatan (42 halaman), Manual Petunjuk Asli (16 halaman)

Siemens SIMATIC ET 200SP Manual
Parameters/address space

4.5 Address space

Chronological sequence
The figure shows the chronological sequence for oversampling. The output data present in
the CPU is output in the data cycle after the next one, distributed across the sub-cycles
which are generated on the actual module.
Figure 4-1
4.5
Address space
Configuration options
The following configurations are possible:
● Configuration 1: Without value status
● Configuration 2: With value status
Evaluating the value status
An additional byte is occupied in the input address space if you enable the value status for
the analog module. Bit 0 and 1 in this byte are assigned to the module. They provide
information about the validity of the analog value.
Bit =1: No fault is present on the channel.
Bit =0: The wiring, the value created on the channel, or similar is incorrect.
24
n = output values from bus cycle n
Oversampling
Analog output module AQ 2xU/I HS (6ES7135-6HB00-0DA1)
Manual, 09/2016, A5E03576140-AD