Juga untuk Siemens SIMATIC ET 200SP: Manual (40 halaman), Panduan Pengguna (21 halaman), Manual (34 halaman), Manual (48 halaman), Manual (30 halaman), Manual (34 halaman), Manual (37 halaman), Manual (36 halaman), Manual (44 halaman), Manual (31 halaman), Manual (35 halaman), Manual (23 halaman), Panduan Konfigurasi (20 halaman), Manual (34 halaman), Manual (29 halaman), Manual (33 halaman), Manual (31 halaman), Panduan Pengguna (32 halaman), Manual (31 halaman), Manual (28 halaman), Manual (41 halaman), Manual (32 halaman), Manual (49 halaman), Manual (24 halaman), Manual (34 halaman), Manual (41 halaman), Manual (30 halaman), Manual (31 halaman), Manual (27 halaman), Manual (24 halaman), Manual (24 halaman), Manual (25 halaman), Manual (49 halaman), Manual (40 halaman), Manual (38 halaman), Manual (39 halaman), Informasi Produk (24 halaman), Manual (32 halaman), Informasi Produk (10 halaman), Panduan Peralatan (43 halaman), Manual (33 halaman), Panduan Peralatan (44 halaman), Petunjuk Pengoperasian Asli (6 halaman), Manual (35 halaman), Manual (28 halaman), Panduan Peralatan (32 halaman), Manual (50 halaman), Manual (30 halaman), Manual (26 halaman), Manual (28 halaman), Manual (34 halaman), Manual (44 halaman), Manual (33 halaman), Panduan Peralatan (42 halaman), Manual Petunjuk Asli (16 halaman)

Siemens SIMATIC ET 200SP Informasi Produk
PROFIsafe address
Every → fail-safe module has a PROFIsafe address. You have to configure the PROFIsafe
address.
PROFIsafe monitoring time
Monitoring time for safety-related communication between the F-CPU and F-I/O
Proof-test interval
Period after which a component must be forced to fail-safe state, that is, it is either replaced
with an unused component, or is proven faultless.
P-switch
→ M-switch
Redundancy, availability-enhancing
Multiple instances of components with the objective of maintaining component functionality in
the event of hardware faults.
Redundancy, safety-enhancing
Multiple availability of components with the aim of exposing hardware faults based on
comparison; such as → 1oo2 evaluation in → fail-safe modules.
Reintegration
After the elimination of a fault, it is necessary to ensure the reintegration (depassivation) of
the → F-I/O. Reintegration (switchover from fail-safe values to process values) occurs either
automatically or only after a user acknowledgment in the safety program.
In the case of a fail-safe input module, the process values pending at the fail-
 s afe inputs are
made available to the
 s afety program again after reintegration. In the case of a fail-safe
output module, the → fail-safe system transfers the output values in the safety program to the
fail-safe outputs again.
Safe state
The basic principle of the safety concept in F-systems is the existence of a safe state for all
process variables. For the digital F-I/O, for example, the safe state is the value "0".
ET 200SP distributed I/O system
Product Information, 07/2013, A5E32288220-AA
Glossary
35