Juga untuk Siemens SIMATIC ET 200SP: Manual (40 halaman), Panduan Pengguna (21 halaman), Manual (34 halaman), Manual (48 halaman), Manual (30 halaman), Manual (34 halaman), Informasi Produk (38 halaman), Manual (37 halaman), Manual (44 halaman), Manual (31 halaman), Manual (35 halaman), Manual (23 halaman), Panduan Konfigurasi (20 halaman), Manual (34 halaman), Manual (29 halaman), Manual (33 halaman), Manual (31 halaman), Panduan Pengguna (32 halaman), Manual (31 halaman), Manual (28 halaman), Manual (41 halaman), Manual (32 halaman), Manual (49 halaman), Manual (24 halaman), Manual (34 halaman), Manual (41 halaman), Manual (30 halaman), Manual (31 halaman), Manual (27 halaman), Manual (24 halaman), Manual (24 halaman), Manual (25 halaman), Manual (49 halaman), Manual (40 halaman), Manual (38 halaman), Manual (39 halaman), Informasi Produk (24 halaman), Manual (32 halaman), Informasi Produk (10 halaman), Panduan Peralatan (43 halaman), Manual (33 halaman), Panduan Peralatan (44 halaman), Petunjuk Pengoperasian Asli (6 halaman), Manual (35 halaman), Manual (28 halaman), Panduan Peralatan (32 halaman), Manual (50 halaman), Manual (30 halaman), Manual (26 halaman), Manual (28 halaman), Manual (34 halaman), Manual (44 halaman), Manual (33 halaman), Panduan Peralatan (42 halaman), Manual Petunjuk Asli (16 halaman)

Siemens SIMATIC ET 200SP Manual
Wiring
3.1 Terminal assignment of the I/O module DQ 16x24VDC/0.5A HA
General pin assignment
Table 3-1
Pin assignment of the DQ 16×24VDC/0.5A HA
Terminal
Assignment
1
DQ a/DQ.0+
3
DQ a/DQ.2+
5
DQ a/DQ.4+
7
DQ a/DQ.6+
9
DQ b/DQ.0+
11
DQ b/DQ.2+
13
DQ b/DQ.4+
15
DQ b/DQ.6+
17
M
19
M
21
M
23
M
25
M
27
M
29
M
31
M
1P1
L+
2P1
L+
1
1-wire
If the module is plugged into a TB45R-P32 terminal block suitable for IO redundancy, the potential at this terminal is 1P3.
1
Note
The M terminals are intended exclusively for the 1 or 2-wire connection system. You may not
use these terminals as the ground terminals for other devices in the system. Ensure that the
total current does not exceed 2A for each M terminal.
10
Terminal
Assignment
2
DQ a/DQ.1+ DQ a /DQ.n+: Output signal, channel n (0...7)
4
DQ a/DQ.3+
6
DQ a/DQ.5+
8
DQ a/DQ.7+
10
DQ b/DQ.1+
12
DQ b/DQ.3+
14
DQ b/DQ.5+
16
DQ b/DQ.7+
18
M
20
M
22
M
24
M
26
M
28
M
30
M
32
M
1P2
M
2P2
M
Description
DQ b /DQ.n+: Output signal, channel n (8...15)
M: Ground
1P1: Supply voltage L+ of the voltage bus 1P
2P1: Supply voltage L+ of the voltage bus 2P
1P2: Ground reference of the voltage bus 1P
2P2: Ground reference of the voltage bus 2P
1 DQ.0+
2
DQ.1+
3 DQ.2+
4
DQ.3+
5 DQ.4+
DQ.5+
6
7 DQ.6+
DQ.7+
8
9 DQ.0+
DQ.1+
10
11 DQ.2+
DQ.3+
12
13 DQ.4+
DQ.5+
14
15 DQ.6+
DQ.7+
16
17
18
19
20
21
22
23
24
26
25
27
28
29
30
31
32
1P1 L+ 24VDC
M 1P2
2P1 L+ 24VDC
M 2P2
MAX. 10 A
Digital output module DQ 16x24VDC/0.5A (6DL1132-6BH00-0PH1)
2-wire
Manual, 05/2017, A5E39265993-AA