Juga untuk Siemens SIMATIC ET 200SP: Manual (40 halaman), Panduan Pengguna (21 halaman), Manual (34 halaman), Manual (48 halaman), Manual (30 halaman), Manual (34 halaman), Informasi Produk (38 halaman), Manual (37 halaman), Manual (36 halaman), Manual (31 halaman), Manual (35 halaman), Manual (23 halaman), Panduan Konfigurasi (20 halaman), Manual (34 halaman), Manual (29 halaman), Manual (33 halaman), Manual (31 halaman), Panduan Pengguna (32 halaman), Manual (31 halaman), Manual (28 halaman), Manual (41 halaman), Manual (32 halaman), Manual (49 halaman), Manual (24 halaman), Manual (34 halaman), Manual (41 halaman), Manual (30 halaman), Manual (31 halaman), Manual (27 halaman), Manual (24 halaman), Manual (24 halaman), Manual (25 halaman), Manual (49 halaman), Manual (40 halaman), Manual (38 halaman), Manual (39 halaman), Informasi Produk (24 halaman), Manual (32 halaman), Informasi Produk (10 halaman), Panduan Peralatan (43 halaman), Manual (33 halaman), Panduan Peralatan (44 halaman), Petunjuk Pengoperasian Asli (6 halaman), Manual (35 halaman), Manual (28 halaman), Panduan Peralatan (32 halaman), Manual (50 halaman), Manual (30 halaman), Manual (26 halaman), Manual (28 halaman), Manual (34 halaman), Manual (44 halaman), Manual (33 halaman), Panduan Peralatan (42 halaman), Manual Petunjuk Asli (16 halaman)

Siemens SIMATIC ET 200SP Manual
Product overview
2.1 Properties of the I/O module DI 16x24VDC HA
Properties
The I/O module has the following technical properties:
● 16 digital inputs with the following properties that can be individually configured for each
channel
– Pulse stretching
– Diagnostics
– Input delay
– Hardware interrupts for positive and negative edges
● Sink input (PNP, active high)
● Module-specific configurable diagnostics for missing supply voltage L+
● Suitable for connecting switches and 2-wire sensors according to IEC 61131-2, types 1 and
3
The I/O module supports the following functions:
● Firmware update
● I&M identification data
● Parameter reassignment in RUN
● Value status QI
● IO redundancy
● Time stamping with 1 ms accuracy
● Output disable switch
You can configure the I/O module with HW Config and integrate it into your system.
Output disable switch
If you want to pull the I/O module in runtime, you have to press the output disable switch for
3 seconds for the I/O module to be deenergized.
When the output disable switch has been pressed for 3 seconds, the LED DIAG flashes red,
the LED MT lights up yellow and the I/O module generates a diagnostics message. See section
Status and error displays of the I/O module DI 16x24VDC HA (Page 21).
Note
Pressing the output disable switch interrupts any ongoing firmware update. A firmware update
cannot be performed when the device is deenergized.
Accessories
The following accessories must be ordered separately:
● Labeling strips
● Color-coded labels