Juga untuk Siemens SIMATIC ET 200SP: Manual (40 halaman), Panduan Pengguna (21 halaman), Manual (34 halaman), Manual (48 halaman), Manual (30 halaman), Manual (34 halaman), Informasi Produk (38 halaman), Manual (37 halaman), Manual (36 halaman), Manual (44 halaman), Manual (31 halaman), Manual (23 halaman), Panduan Konfigurasi (20 halaman), Manual (34 halaman), Manual (29 halaman), Manual (33 halaman), Manual (31 halaman), Panduan Pengguna (32 halaman), Manual (31 halaman), Manual (28 halaman), Manual (41 halaman), Manual (32 halaman), Manual (49 halaman), Manual (24 halaman), Manual (34 halaman), Manual (41 halaman), Manual (30 halaman), Manual (31 halaman), Manual (27 halaman), Manual (24 halaman), Manual (24 halaman), Manual (25 halaman), Manual (49 halaman), Manual (40 halaman), Manual (38 halaman), Manual (39 halaman), Informasi Produk (24 halaman), Manual (32 halaman), Informasi Produk (10 halaman), Panduan Peralatan (43 halaman), Manual (33 halaman), Panduan Peralatan (44 halaman), Petunjuk Pengoperasian Asli (6 halaman), Manual (35 halaman), Manual (28 halaman), Panduan Peralatan (32 halaman), Manual (50 halaman), Manual (30 halaman), Manual (26 halaman), Manual (28 halaman), Manual (34 halaman), Manual (44 halaman), Manual (33 halaman), Panduan Peralatan (42 halaman), Manual Petunjuk Asli (16 halaman)

Siemens SIMATIC ET 200SP Manual
B.3

Representation of analog values in the current measuring ranges

The following tables list the decimal and hexadecimal values (codes) of the possible current
measuring ranges.
Table B- 4
Values
Dec.
32767
32511
27649
27648
20736
1
0
-1
-20736
-27648
-27649
-32512
-32768
Table B- 5
Values
Dec.
32767
32511
27649
27648
20736
1
0
-1
-4864
-32768
* For measurement type "2-wire transducer", negative values are not possible for the range "0 to
20 mA". Therefore, no underrange or underflow exists here.
Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1)
Manual, 12/2015, A5E36104399-AA
B.3 Representation of analog values in the current measuring ranges
Current measuring range ±20 mA
Current measuring range
Hex.
±20 mA
7FFF
> 23.52 mA
7EFF
23.52 mA
6C01
6C00
20 mA
5100
15 mA
1
723.4 nA
0
0 mA
FFFF
AF00
-15 mA
9400
-20 mA
93FF
8100
-23.52 mA
8000
< -23.52 mA
Current measuring ranges 0 to 20 mA and 4 to 20 mA
Current measuring range
Hex.
0 to 20 mA*
7FFF
> 23.52 mA
7EFF
23.52 mA
6C01
6C00
20 mA
5100
15 mA
1
723.4 nA
0
0 mA
FFFF
ED00
-3.52 mA
8000
< -3.52 mA
Representation of analog values
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
Range
4 to 20 mA
> 22.81 mA
Overflow
22.81 mA
Overrange
20 mA
Nominal range
16 mA
4 mA + 578.7 nA
4 mA
Underrange
1.185 mA
< 1.185 mA
Underflow
35