Juga untuk Siemens SIMATIC ET 200SP: Manual (40 halaman), Panduan Pengguna (21 halaman), Manual (34 halaman), Manual (48 halaman), Manual (30 halaman), Manual (34 halaman), Informasi Produk (38 halaman), Manual (37 halaman), Manual (36 halaman), Manual (44 halaman), Manual (31 halaman), Manual (35 halaman), Manual (23 halaman), Panduan Konfigurasi (20 halaman), Manual (34 halaman), Manual (29 halaman), Manual (33 halaman), Manual (31 halaman), Panduan Pengguna (32 halaman), Manual (31 halaman), Manual (28 halaman), Manual (32 halaman), Manual (49 halaman), Manual (24 halaman), Manual (34 halaman), Manual (41 halaman), Manual (30 halaman), Manual (31 halaman), Manual (27 halaman), Manual (24 halaman), Manual (24 halaman), Manual (25 halaman), Manual (49 halaman), Manual (40 halaman), Manual (38 halaman), Manual (39 halaman), Informasi Produk (24 halaman), Manual (32 halaman), Informasi Produk (10 halaman), Panduan Peralatan (43 halaman), Manual (33 halaman), Panduan Peralatan (44 halaman), Petunjuk Pengoperasian Asli (6 halaman), Manual (35 halaman), Manual (28 halaman), Panduan Peralatan (32 halaman), Manual (50 halaman), Manual (30 halaman), Manual (26 halaman), Manual (28 halaman), Manual (34 halaman), Manual (44 halaman), Manual (33 halaman), Panduan Peralatan (42 halaman), Manual Petunjuk Asli (16 halaman)

Siemens SIMATIC ET 200SP Manual
4.4

Address space

Configuration options
The following configurations are possible:
● Configuration 1: Without value status
● Configuration 2: With value status
Evaluating the value status
If you enable the value status for the analog module, an additional byte is occupied in the
input address space. Bits 0 to 3 in this byte are assigned to a channel. They provide
information about the validity of the analog value.
Bit = 1: No fault is present on the channel.
Bit = 0: Channel is disabled or there is a fault/error on the module.
If a fault/error occurs on a channel with this module, the value status for all channels is 0.
Address space
The following figure shows the assignment of the address space for the AI 4×U/I 2-wire ST
with value status (Quality Information (QI)). The addresses for the value status are only
available if the value status is enabled.
Figure 4-2
Analog Input Module AI 4xU/I 2-wire ST (6ES7134-6HD01-0BA1)
Manual, 12/2017, A5E03572832-AD
Address space of the AI 4×U/I 2-wire ST with value status
Parameters/address space
4.4 Address space
21