Juga untuk Siemens SIMATIC ET 200SP: Manual (40 halaman), Panduan Pengguna (21 halaman), Manual (34 halaman), Manual (48 halaman), Manual (30 halaman), Manual (34 halaman), Informasi Produk (38 halaman), Manual (37 halaman), Manual (36 halaman), Manual (44 halaman), Manual (31 halaman), Manual (35 halaman), Manual (23 halaman), Panduan Konfigurasi (20 halaman), Manual (34 halaman), Manual (29 halaman), Manual (33 halaman), Manual (31 halaman), Panduan Pengguna (32 halaman), Manual (31 halaman), Manual (28 halaman), Manual (41 halaman), Manual (32 halaman), Manual (49 halaman), Manual (24 halaman), Manual (34 halaman), Manual (41 halaman), Manual (30 halaman), Manual (31 halaman), Manual (27 halaman), Manual (24 halaman), Manual (24 halaman), Manual (25 halaman), Manual (40 halaman), Manual (38 halaman), Manual (39 halaman), Informasi Produk (24 halaman), Manual (32 halaman), Informasi Produk (10 halaman), Panduan Peralatan (43 halaman), Manual (33 halaman), Panduan Peralatan (44 halaman), Petunjuk Pengoperasian Asli (6 halaman), Manual (35 halaman), Manual (28 halaman), Panduan Peralatan (32 halaman), Manual (50 halaman), Manual (30 halaman), Manual (26 halaman), Manual (28 halaman), Manual (34 halaman), Manual (44 halaman), Manual (33 halaman), Panduan Peralatan (42 halaman), Manual Petunjuk Asli (16 halaman)

Siemens SIMATIC ET 200SP Manual
The following parameter settings are possible:
Table 4- 2
Configurable parameters and their defaults (GSD file)
Parameter
Sampling rate
Diagnostics:
No supply voltage L+
Diagnostics:
Short-circuit to ground
Diagnostics:
Overflow
Diagnostics:
Underflow
Diagnostics:
Wire break
Type/range of measu-
rement
Smoothing
Analog input module AI 2xU/I 2-/4-wire HS (6ES7134-6HB00-0DA1)
Manual, 09/2018, A5E03576060-AF
Value range
1 value/cycle
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Deactivated
Voltage 1 to 5 V
Voltage +/- 5 V
Voltage +/- 10 V
Voltage 0 to 10 V
Current (4-wire transducer)
0 to 20 mA
Current (4-wire transducer)
+/- 20 mA
Current (4-wire transducer)
4 to 20 mA
Current (2-wire transducer)
0 to 20 mA
Current (2-wire transducer)
4 to 20 mA
None
2 times
4 times
8 times
16 times
32 times
64 times
Default
Reconfigura-
tion in RUN
1 value/cycle
No
Disable
Yes
Disable
Yes
Disable
Yes
Disable
Yes
Disable
Yes
Current (4-
Yes
wire trans-
ducer) 4 to
20 mA
None
Yes
Parameters/address space
4.2 Parameters
Effective range with configurati-
on software, e.g. STEP 7
(TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Module
Module
Channel
Channel
Channel
Channel
Channel
Channel
1
Channel
Channel
Channel
Channel
Channel
Channel
Channel
17