Juga untuk Siemens SIMATIC ET 200SP: Manual (40 halaman), Panduan Pengguna (21 halaman), Manual (34 halaman), Manual (48 halaman), Manual (30 halaman), Manual (34 halaman), Informasi Produk (38 halaman), Manual (37 halaman), Manual (36 halaman), Manual (44 halaman), Manual (31 halaman), Manual (35 halaman), Manual (23 halaman), Panduan Konfigurasi (20 halaman), Manual (34 halaman), Manual (29 halaman), Manual (33 halaman), Manual (31 halaman), Panduan Pengguna (32 halaman), Manual (31 halaman), Manual (28 halaman), Manual (41 halaman), Manual (32 halaman), Manual (49 halaman), Manual (24 halaman), Manual (34 halaman), Manual (41 halaman), Manual (30 halaman), Manual (31 halaman), Manual (27 halaman), Manual (24 halaman), Manual (24 halaman), Manual (25 halaman), Manual (49 halaman), Manual (40 halaman), Manual (38 halaman), Manual (39 halaman), Informasi Produk (24 halaman), Manual (32 halaman), Informasi Produk (10 halaman), Panduan Peralatan (43 halaman), Manual (33 halaman), Panduan Peralatan (44 halaman), Petunjuk Pengoperasian Asli (6 halaman), Manual (35 halaman), Manual (28 halaman), Panduan Peralatan (32 halaman), Manual (50 halaman), Manual (30 halaman), Manual (26 halaman), Manual (28 halaman), Manual (34 halaman), Manual (33 halaman), Panduan Peralatan (42 halaman), Manual Petunjuk Asli (16 halaman)

Siemens SIMATIC ET 200SP Manual
First BaseUnit of an ET 200SP in the configuration (as of V3.1)
Note
First BaseUnit of an ET 200SP in the configuration
The first BaseUnit of an ET 200SP station may be a dark-colored one, if an AC I/O module
or AI Energy Meter ST is plugged. Please observe the information on limiting the overvoltage
and power rating in the AC I/O module manuals.
A light-colored BaseUnit must be plugged into the slot of the first 24 V DC I/O module in
order to route the 24 V DC supply voltage via a fuse.
Note the type of the BaseUnits during the configuration.
Value status (quality information, QI)
Note
The DI 8x24VDC HF (V1.1), DQ 8x24VDC/0,5A HF (V1.1), AI 2xU/I 2-/4-wire HS,
AI 4xRTD/TC 2-/3-/4-wire HF (V1.1) and AQ 2xU/I HS I/O modules can evaluate the value
status (Quality Information, QI).
Reaction times for fail-safe modules
The following maximum reaction time of the interface module must be taken into account
when calculating the reaction times of fail-safe modules:
maximum reaction time = configured update time + 400 μs (but at least 1.4 ms)
Fail-safe modules are not compatible replacement parts
The DI 8x24VDC HF (V1.2) and DQ 8x24VDC/0,5A HF (V1.2) I/O modules are not
compatible replacement parts for I/O modules with firmware V1.1 or 1.0.
You need to re-configure these DI 8x24VDC HF (V1.2) and DQ 8x24VDC/0,5A HF (V1.2)
I/O modules.
IM 155-6 PN ST interface module (6ES7155-6AU00-0BN0)
Manual, 12/2014, A5E03576904-AC
23BCompatibility