Juga untuk Siemens SIMATIC ET 200SP HA: Manual (50 halaman), Manual (34 halaman), Manual (38 halaman), Panduan Peralatan (44 halaman), Panduan Peralatan (50 halaman), Panduan Peralatan (38 halaman), Panduan Peralatan (46 halaman), Panduan Peralatan (42 halaman), Panduan Peralatan (44 halaman), Panduan Peralatan (36 halaman), Panduan Peralatan (38 halaman)

Siemens SIMATIC ET 200SP HA Manual

Wiring

3.1

Pin assignment

24 V DC supply voltage
The following table shows the signal names and the descriptions of the pin assignment for a
24 V DC supply voltage.
Table 3-1
1L+ and 2L+ as well as 1M and 2M are bridged internally.
1
Maximum 10 A permitted.
2
Each interface module has its own 24 V connection.
PROFINET IO with BusAdapter BA 2×RJ45
The following table shows the signal name and designation of the pin assignment of the
BusAdapter BA 2×RJ45.
Table 3-2
Interface Module IM 155-6 PN HA (6DL1155-6AU00-0PM0)
Manual, 05/2017, A5E39262148-AA
Pin assignment 24 V DC supply voltage
View
Plug
IM connection
Pin assignment of PROFINET IO with BusAdapter BA 2×RJ45
View
Signal name
Description
1
1L+
24 V DC
2L+
24 V DC (for looping through)
1M
Ground
2M
Ground (for looping through)
Signal name
1
TD
Transmit data +
2
TD_N
Transmit data –
3
RD
Receive data +
4
GND
Ground
5
GND
Ground
6
RD_N
Receive data –
7
GND
Ground
8
GND
Ground
3
2
2
Description
11