Juga untuk Siemens SIMATIC ET 200SP HA: Manual (32 halaman), Manual (34 halaman), Manual (38 halaman), Panduan Peralatan (44 halaman), Panduan Peralatan (50 halaman), Panduan Peralatan (38 halaman), Panduan Peralatan (46 halaman), Panduan Peralatan (42 halaman), Panduan Peralatan (44 halaman), Panduan Peralatan (36 halaman), Panduan Peralatan (38 halaman)

Siemens SIMATIC ET 200SP HA Manual
Parameters

4.2 Module/channel parameters

4.2
Module/channel parameters
Parameters of the DI 16xNAMUR HA
You have the following setting options:
Table 4-1
Parameters and their default settings
Parameters
Diagnostics,
Missing supply voltage L
+
IO redundancy
Diagnostics
Short-circuit
Diagnostic
Wire break
Diagnostic
Change-over contact er‐
ror
Diagnostic
Flutter error
Flutter monitoring: Moni‐
toring window
Flutter monitoring: Num‐
ber of signal changes
Hardware interrupts
Encoder type
16
Value range
● Enabled
● Disabled
● None
● 2 modules
● Enabled
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
● 0.5 s
● 1 s to 100 s (can be set in
1 s-increments)
● Disabled
● 2 to 32
● Disabled
● Rising edge
● Falling edge
● Falling and rising edge
● Channel disabled
● NAMUR sensor
● Single contact,
unconnected
● Single contact, connected
with 10 kΩ
● NAMUR change-over
contact
● Change-over contact,
unconnected
● Change-over contact,
connected with 10 kΩ
Default
Changing parameter
settings in RUN
Enabled
Yes
None
Yes
Enabled
Yes
Enabled
Yes
Disabled
Yes
Disabled
Yes
0.5 s
Yes
Disabled
Yes
Disabled
Yes
NAMUR sensor
Yes
Digital Input Module DI 16xNAMUR HA (6DL1131-6TH00-0PH1)
Efficiency range
Module
Module
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Manual, 11/2017, A5E39293880-AB