Juga untuk Siemens SIMATIC ET 200SP HA: Manual (32 halaman), Manual (50 halaman), Manual (34 halaman), Manual (38 halaman), Panduan Peralatan (44 halaman), Panduan Peralatan (50 halaman), Panduan Peralatan (38 halaman), Panduan Peralatan (42 halaman), Panduan Peralatan (44 halaman), Panduan Peralatan (36 halaman), Panduan Peralatan (38 halaman)

Siemens SIMATIC ET 200SP HA Panduan Peralatan
Parameters

6.3 Explanation of the module/channel parameters

Parameter
Pulse stretching (Page 22)
Hardware interrupts positive
edge (Page 23)
2
Hardware interrupts nega‐
tive edge (Page 24)
2
Potential group (Page 24)
The wire break diagnostics can only be enabled when the "Check for wire break" parameter is enabled. If you use a simple
1
encoder contact, you need to connect a parallel resistor to enable wire break diagnostics in the open state (sensor resistance
for wire break diagnostics: 15 kΩ to 18 kΩ).
The input delay is switched off on all channels when high precision time stamping is activated. When high precision time
2
stamping is activated, pulse stretching and the rising/falling edge hardware interrupt are deactivated on all channels (not
adjustable).
6.2

Parameter reassignment

Definition
Each configuration change resets the corresponding reaction. Changing the configuration of a
function does not affect other functions.
6.3
Explanation of the module/channel parameters
6.3.1

Diagnostics, Missing supply voltage L+

Definition
Enabling of the diagnostics for missing or insufficient supply voltage L+.
20
Value range
2
None
0.05 s
0.1 s
0.2 s
0.5 s
1 s
2 s
Enabled
Disabled
Enabled
Disabled
Potential group of the left mod‐
ule (dark gray terminal block)
New potential group (light gray
terminal block)
No potential group (black termi‐
nal block)
Default
Parameter re‐
assignment in
RUN
None
Yes
Disabled
Yes
Disabled
Yes
Use potential
No
group of the left
module
Equipment Manual, 10/2020, A5E39265608-AD
Efficiency range
Channel
Channel
Channel
Module
DI 16x24VDC HA