Parameters
6.3 Explanation of the module/channel parameters
Parameters
Potential group (Page 21)
Double-width terminal
block (Page 22)
2
Only applicable when the value "Output substitute value" has been enabled for the "Reaction to CPU STOP" parameter.
1
I/O module on terminal block with potential distributor: Select the "Double-width terminal block" parameter in the hardware
2
properties for the I/O module.
6.3
Explanation of the module/channel parameters
6.3.1
Diagnostics, Missing supply voltage L+
Definition
Enabling of the diagnostics for missing or insufficient supply voltage L+.
6.3.2
Diagnostics, Short-circuit to ground
Definition
When the digital output is enabled, you can enable diagnostics that report a digital output short
circuit to M.
A short circuit to M is only recognized when the output is switched on (output value = 1).
Note
Short-circuit signal
If the output is disabled with pending short circuit (output value = 0), the diagnostics Short-
circuit to M is reset.
20
Value range
•
Potential group of the left mod‐
ule (dark gray terminal block)
•
New potential group (light gray
terminal block)
•
No potential group (black termi‐
nal block)
•
Enabled
•
Disabled
Default
Parameter re‐
assignment in
Use potential
No
group of the left
module
Disabled
No
Equipment Manual, 08/2019, A5E48262762-AB
Efficiency range
RUN
Module
Configuration (HW
Config)
DQ 32x24VDC/0.5A HA