Siemens Simatic S7-1500 Manual - Halaman 39

Jelajahi secara online atau unduh pdf Manual untuk Peralatan Industri Siemens Simatic S7-1500. Siemens Simatic S7-1500 40 halaman. Digital output module dq 16x230vac/2a st relais (6es7522-5hh00-0ab0)
Juga untuk Siemens Simatic S7-1500: Manual (37 halaman), Manual (47 halaman), Manual (24 halaman), Manual (34 halaman), Panduan Pengguna (45 halaman), Manual (27 halaman), Panduan Konfigurasi (20 halaman), Manual (47 halaman), Manual (43 halaman), Manual (48 halaman), Manual (26 halaman), Manual (28 halaman), Manual (50 halaman), Manual (34 halaman), Panduan Pengguna (44 halaman), Manual (50 halaman), Manual (30 halaman), Manual (41 halaman), Manual (50 halaman), Manual (40 halaman), Manual Pemrograman Keselamatan (48 halaman), Panduan Instruksi Komunikasi (36 halaman), Manual (40 halaman), Manual (25 halaman), Manual (42 halaman), Deskripsi Aplikasi (50 halaman), Manual (28 halaman), Manual (33 halaman), Manual (49 halaman), Manual (36 halaman), Manual (41 halaman), Manual (46 halaman), Manual (38 halaman), Manual (35 halaman), Manual (39 halaman), Manual (28 halaman), Manual (35 halaman), Panduan Peralatan (35 halaman), Manual (50 halaman), Panduan Peralatan (32 halaman), Panduan Peralatan (38 halaman), Manual (29 halaman), Panduan Peralatan (38 halaman), Manual (34 halaman), Manual (36 halaman), Panduan Peralatan (50 halaman), Manual (45 halaman)

Siemens Simatic S7-1500 Manual
C.3

Representation of analog values in the current output ranges

The tables below list the decimal and hexadecimal values (codes) of the possible current
output ranges.
Table C- 7
Values
>117.589%
117.589%
100%
75%
0.003617%
0%
-75%
-100%
-117.593%
<-117.593%
Table C- 8
Values
>117.589%
117.589%
100%
75%
0.003617%
0%
<0%
Analog output module AQ 4xU/I ST (6ES7532-5HD00-0AB0)
Manual, 09/2016, A5E03484696-AD
C.3 Representation of analog values in the current output ranges
Current output range ±20 mA
dec
hex
>32511
>7EFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-20736
AF00
-27648
9400
-27649
93FF
-32512
8100
<-32512
<8100
Current output range 0 mA to 20 mA
dec
hex
>32511
>7EFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
<0
<0
Representation of analog values
Current output range
±20 mA
23.52 mA
23.52 mA
20 mA
15 mA
723.4 nA
0 mA
-723.4 nA
-15 mA
-20 mA
-23.52 mA
-23.52 mA
Current output range
0 mA to 20 mA
23.52 mA
23.52 mA
20 mA
15 mA
723.4 nA
0 mA
0 mA
Range
Maximum output value
Overshoot range
Rated range
Undershoot range
Minimum output value
Range
Maximum output value
Overshoot range
Rated range
Minimum output value
39