Juga untuk Siemens Simatic S7-1500: Manual (40 halaman), Manual (37 halaman), Manual (47 halaman), Manual (24 halaman), Manual (34 halaman), Panduan Pengguna (45 halaman), Manual (27 halaman), Panduan Konfigurasi (20 halaman), Manual (47 halaman), Manual (43 halaman), Manual (48 halaman), Manual (26 halaman), Manual (28 halaman), Manual (50 halaman), Manual (34 halaman), Manual (50 halaman), Manual (30 halaman), Manual (41 halaman), Manual (50 halaman), Manual (40 halaman), Manual Pemrograman Keselamatan (48 halaman), Panduan Instruksi Komunikasi (36 halaman), Manual (40 halaman), Manual (25 halaman), Manual (42 halaman), Deskripsi Aplikasi (50 halaman), Manual (28 halaman), Manual (33 halaman), Manual (49 halaman), Manual (36 halaman), Manual (41 halaman), Manual (46 halaman), Manual (38 halaman), Manual (35 halaman), Manual (39 halaman), Manual (28 halaman), Manual (35 halaman), Panduan Peralatan (35 halaman), Manual (50 halaman), Panduan Peralatan (32 halaman), Panduan Peralatan (38 halaman), Manual (29 halaman), Panduan Peralatan (38 halaman), Manual (34 halaman), Manual (36 halaman), Panduan Peralatan (50 halaman), Manual (45 halaman)

Siemens Simatic S7-1500 Panduan Pengguna
Properties
The module has the following technical properties:
● 16 digital outputs, electrically isolated in groups of 8
● Rated output voltage 24 V DC
● Rated output current 0.5 A per channel
● Configurable substitute values (per channel)
● Configurable diagnostics (per channel)
● Suitable for solenoid valves, DC contactors, and indicator lights
● Switching cycle counter for connected actuators, e.g. solenoid valves
● Hardware compatible with digital output module DQ 16x24VDC/0.5A ST
(6ES7522-1BH00-0AB0).
The module supports the following functions:
Table 2- 1
Version dependencies of the module functions
Function
Firmware update
Identification data I&M0 to I&M3
Parameter assignment in RUN
Isochronous mode
Module-internal Shared Output
(MSO)
Configurable submodules / sub-
modules for Shared Device
Switching cycle counter
You can configure the module with STEP 7 (TIA Portal) and with a GSD file.
Compatibility
The following table shows the compatibility of the modules and the dependencies between
hardware functional status (FS) and firmware version (FW) used:
Hardware functional status
FS01
FS02
Digital output module DQ 16x24VDC/0.5A HF (6ES7522-1BH01-0AB0)
Manual, 06/2018, A5E35683409-AC
Firmware version
of the module
(TIA Portal) as of V13, SP1
V1.0.0 or higher
V1.0.0 or higher
V1.0.0 or higher
V1.0.0 or higher
V1.0.0 or higher
(PROFINET IO only)
V1.0.0 or higher
(PROFINET IO only)
V1.1.0 or higher
as of V15.0 with HSP0247
PROFINET IO only
Central operation with a
S7-1500 CPU is supported
Firmware version
V1.0.0
V1.1.0
Configuration software
STEP 7
with HSP 0143
X
X
X
X
X
X
Note
Upgrade to V1.1.0 not possible
Upgrade and downgrade possible between
V1.1.0 and higher
Product overview
2.1 Properties
GSD file in STEP 7
(TIA Portal) V12 or higher, or
STEP 7 V5.5 SP3 or higher
--- / X
X
X
---
X
(PROFINET IO only)
X
(PROFINET IO only)
X
(PROFINET IO only)
11