4.2
Parameters
Parameters of AI 16xU BA
When you assign the module parameters in STEP 7, you use various parameters to specify the
module properties. The following table lists the configurable parameters. The effective range
of the configurable parameters depends on the type of configuration. The following
configurations are possible:
• Central operation with a S7-1500 CPU
• Distributed operation on PROFINET IO in an ET 200MP system
• Distributed operation on PROFIBUS DP in an ET 200MP system
When assigning parameters in the user program, use the WRREC instruction to transfer the
parameters to the module by means of data records; refer to the section Parameter
assignment and structure of the parameter data records (Page 32).
The following parameter settings for the channels are possible:
Table 4- 2
Configurable parameters and their defaults
Parameters
Diagnostics
•
Overflow
•
Underflow
•
Common mode error
•
Wire break
1)
Measuring
•
Measurement type
•
Measuring range
•
Interference frequency
suppression
•
Smoothing
Analog input module AI 16xU BA (6ES7531-7LH00-0AB0)
Equipment Manual, 09/2020, A5E47052556-AA
Range of values
Default
setting
Yes/No
No
Yes/No
No
Yes/No
No
Yes/No
No
Voltage
Voltage
±1 V
±10 V
1 to 5 V
±5 V
±10 V
400 Hz
50 Hz
60 Hz
50 Hz
10 Hz
None/low/medium/hi
None
gh
Parameter as-
Scope with configuration soft-
signment in
ware, e.g., STEP 7 (TIA Portal)
RUN
GSD file
PROFINET IO
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Parameters/address space
4.2 Parameters
GSD file
PROFIBUS DP
Module
2)
Module
2)
Module
2)
Module
2)
Channel
Channel
Module
Channel
13