9 Troubleshooting
Troubleshooting
9
I can't go online with the drive in Starter using the
9.1
Ethernet cable.
Do you have firmware v4.7 or above on the drive unit? Communication from Starter
to the drive using Ethernet/IP is only support with firmware v4.7 or later on the
G120. If you are using v4.6, then you will need to use the USB cable to connect to
the drive with Starter.
9.2
The drive and the PLC are not communicating
Figure 9-1
Figure 9-2
1. Check the LED lights
a. PLC: Is the I/O light solid green?
b. G120: Is the Link1 light solid green?
c. This means that the drive is communicating and it is another issue
2. Is the drive set for EIP (G120: p2030 = 10)?
a. A power cycle is required after changing p2030.
SINAMICS G: Control of a G120 with an Allen-Bradley controller
(Compact/ ControlLogix with RSLogix 5000) via EtherNet/IP