Juga untuk Siemens SINAMICS G130: Panduan Petunjuk Pengoperasian (24 halaman), Panduan Petunjuk Pengoperasian (26 halaman), Panduan Petunjuk Pengoperasian (46 halaman), Panduan Petunjuk Pengoperasian (24 halaman), Panduan Petunjuk Pengoperasian (31 halaman), Panduan Petunjuk Pengoperasian (30 halaman), Panduan Petunjuk Pengoperasian (28 halaman), Panduan Petunjuk Pengoperasian (30 halaman), Panduan Petunjuk Pengoperasian (22 halaman), Panduan Petunjuk Pengoperasian (28 halaman), Panduan Petunjuk Pengoperasian (30 halaman), Panduan Petunjuk Pengoperasian (34 halaman), Panduan Petunjuk Pengoperasian (46 halaman), Panduan Petunjuk Pengoperasian (26 halaman), Panduan Petunjuk Pengoperasian (26 halaman), Panduan Petunjuk Pengoperasian (28 halaman), Panduan Petunjuk Pengoperasian (42 halaman), Panduan Petunjuk Pengoperasian (46 halaman), Panduan Petunjuk Pengoperasian (24 halaman), Panduan Petunjuk Pengoperasian (24 halaman), Panduan Petunjuk Pengoperasian (30 halaman), Panduan Petunjuk Pengoperasian (42 halaman), Panduan Petunjuk Pengoperasian (38 halaman), Panduan Petunjuk Pengoperasian (28 halaman), Panduan Petunjuk Pengoperasian (22 halaman), Panduan Petunjuk Pengoperasian (24 halaman)

Siemens SINAMICS G130 Panduan Petunjuk Pengoperasian
Cable cross-sections
Table 4- 1
Cable cross-sections for connections between the dv/dt filter plus Voltage Peak Limiter and Power Module
dv/dt filter plus Voltage Peak
Limiter
6SL3000-2DE32-6AA0
6SL3000-2DE35-0AA0
6SL3000-2DE38-4AA0
6SL3000-2DE41-4AA0
6SL3000-2DH31-0AA0
6SL3000-2DH32-2AA0
6SL3000-2DH33-3AA0
6SL3000-2DH34-1AA0
6SL3000-2DH35-8AA0
6SL3000-2DH38-1AA0
CAUTION
The connection to the DC link of the Power Module must be routed according to IEC
61800-5-2:2007, Table D.1 in order to rule out short-circuiting or ground faults.
This can be accomplished, for example, by:
• Eliminating the risk of mechanical damage to the cables
• Using cables with double insulation
• Maintaining adequate clearance, using spacers, for example
• Routing the cables in separate cable ducts or tubes
Note
The connections should be kept as short as possible.
The maximum cable length for the connections specified in the table above is 5 m.
dV/dt filter plus Voltage Peak Limiter
Operating Instructions, 03/2012, A5E00692302A
Connection to the DC link
(DCPS/DCNS)
[mm²]
Line voltage 380 V – 480 V 3 AC
35
70
2 x 50
2 x 120
Line voltage 500 V – 600 V 3 AC and 660 V – 690 V 3 AC
16
16
70
120
120
2 x 70
Electrical installation
Connection between dv/dt reactor and
Voltage Peak Limiter
(1U2, 1V2, 1W2) [mm²]
10
16
50
120
6
6
16
35
35
70