Prerequisites
1. Set the "1.YFCT" parameter of the positioner to "ncSLL".
2. Launch initialization as usual with "INITA".
7

Technical specifications

Additional modules
Actuating range
● Linear actuator
● Part-turn actuator
Linearity (after corrections made by
positioner)
● Linear actuator
● Part-turn actuator
Hysteresis
Continuous operation temperature
Vibration resistance
● Harmonics oscillation
(sine wave) to
DIN EN 60068-2-6/05.96
Enclosure protection type
For connecting to circuits with the
following peak values
Certificates and approvals
CE conformity
Explosion protection
Explosion protection in accordance
with
Intrinsic safety "ia"
Installation location
● Intrinsic safety "ia"
Permissible ambient temperature
SIPART PS2 Non-Contacting Sensor (NCS)
A5E00097485-07, 01/2012
Without explosion protection
3 ... 130 mm (0.12 ... 5.12"); up to 200 mm (7.87") on request
-40 °C to +85 °C (-40 °F to +185 °F);
extended temperature range on request
7 mm (0.28"), 5 to 54 Hz; 500 m/s
IP68 according to IEC EN 60529; NEMA 4X / Encl. Type 4X
-
The relevant directives and standards applied, including their revision levels, are
available on the Internet in our EC Declaration of Conformity.
Ex labels
ATEX/IECEx
Zone 1:
II 2 G Ex ia IIC T6/T4 Gb
Zone 1
Zone 1
T4: -40 ... +90 °C (-40 ... +194 °F)
T6: -40 ... +70 °C (-40 ... +158 °F)
With Ex protection
Ex "ia"
30° ... 100°
± 1 %
± 1 %
± 0.2 %
-
(1640 ft/s
), 80 to 200 Hz
2
2
U
= 5 V
i
C
= 10 nF
i
L
= 240 μH
i
FM/CSA
FM:
IS, Class I, Divison 1, ABCD
Class I, Zone 1, AEx ib, IIC,T6/T4
CSA:
Class I, Division 1, ABCD
Class I, Zone 1, Ex ib, IIC
31