3.14 Incoming Line Arrangements -
Main Fusible Switches
Main fusible switches consist of the following:
• 60 to 100A Siemens-Furnas brand switch and class R fuse clips.
• 200 to 600A Siemens molded case switch and class R fuse holder.
• 800 to1200A Siemens molded case switch and class L fuse holder.
Fusible Disconnect
Switch/Clips
Location
60A/30A or 60A
60A/30A or 60A
100A/100A
100A/100A
200A/200A
200A/200A
400A/400A
400A/400A
600A/600A
600A/600A
800A/800A*
800A/800A*
1200A/1200A*
1200A/1200A*
Bottom
* Space in rear of structure not available.
. Optional lugs available. Contact factory for size and rating.
All dimensions are shown in inches unless otherwise specified.
22
Incoming.
Cable Size.
Top
Qty = 1
#14 - #14 CU/AL
Bottom
Qty = 1
#14 - #14 CU/AL
Top
Qty =1
#14 - 1/0 MCM CU
Bottom
Qty = 1
#14 - 1/0 MCM CU
Top
Qty = 1
#6 - 350MCM CU
Bottom
Qty = 1
#6 - 350MCM CU
Top
Qty = 2
3/0 - 500MCM CU
Bottom
Qty = 2
3/0 - 500MCM CU
Top
Qty = 2
3/0 - 500MCM CU
Bottom
Qty = 2
3/0 - 500MCM CU
Top
Qty = 3
250-500MCM CU
Bottom
Qty = 3
250-500MCM CU
Top
Qty = 4
250-500MCM CU
Qty = 4
250-500MCM CU
Fig. Ref.
Wire Bending.
Next Pg.
Space.Dim.A
32
14
37
8
33
13
38
7
34
16
39
10
35
14
40
14
35
14
40
14
36
16
41
22
36
16
41
22
Total Assembly
Required Unit
Height.Dim. B
Space.Dim. C
24
12
24
18
30
18
30
24
42
30
48
42
48
36
60
54
48
36
60
54
60
48
90
72
60
48
90
72
Siemens Energy & Automation, Inc.