Input range (rated value)/input resistance
•
Permitted input current (destruction limit)
Load of the two-wire transmitter:
Smoothing of the measured values
I&M functions
The I&M data can be read from the module using interface modules with the following order
numbers or firmware/product versions (or higher):
Interface module
IM151-1 HIGH FEATURE
IM151-3 PN
IM151-3 PN HIGH FEATURE
IM151-3 PN FO
2 AI I 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0)
Manual, 04/2007, A5E01076111-01
1.1 2AI 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0)
Current
Data for selecting a sensor
Approx. 44 Ω
Approx. 50 mA (can be limited electronically)
Max. 750 Ω
Yes, can be assigned parameters in 4 steps by
means of digital filtering
Step
None
Weak
Medium
Strong
Order number
6ES7151-1BA01-0AB0
6ES7151-3AA20-0AB0
6ES7151-3AA20-0AB0
6ES7151-3BB21-0AB0
Time constant
1 x cycle time
4 x cycle time
16 x cycle time
32 x cycle time
Firmware version
Product version
V2.0
V4.0
V4.0
V4.0
Properties
02
01
01
01
11