Siemens 2AO U HF Manual - Halaman 14
Jelajahi secara online atau unduh pdf Manual untuk Unit Kontrol Siemens 2AO U HF. Siemens 2AO U HF 22 halaman. Analog electronic module simatic et 200s distributed i/o
Diagnostics
3.2 Error types
3.2
Error types
Analog output module error types
Table 3-1
16
D
9
D
1
D
14
Error types
Error type
10000: Parameter assignment
error
01001: Error
00001: Short circuit
Meaning
Module cannot use the
parameter for the
channel:
Inserted module does not
match the one
configured.
Incorrect parameter
assignment.
Internal module error has
occurred (diagnostic
message on channel 0
applies to the entire
module).
Short circuit of the final
controlling element
supply.
2AO U HF analog electronic module (6ES7135-4LB02-0AB0)
Manual, 04/2007, A5E01076940-01
Remedy
Correct the configuration
(align actual and set
configuration).
Correct the parameter
assignment (wire break
diagnostics only
parameterized for the
permitted measuring
ranges).
Replace the module.
Correct the process wiring.