Operation
4.2

Extinguishing process

20
Building Technologies
Fire Safety
In the event of fire, an extinguishing process normally occurs automatically and
triggers the two alarm stages "Fire alarm" and "Activated" before extinguishing is
activated. As explained in the following, there are different operating options to
affect the extinguishing process.
Fire alarm
A fire detector in the extinguishing area has detected a fire.
-
The buzzer in the control unit is activated and the alarm horn signal "Fire alarm"
as a rule with a slow pulsating tone
-
The red Leds "Detector Zone 1" or "Detector Zone 2" light up
-
The red Led "Fire alarm" light up
-
The red Led "Activated" flashes, indicating the pre-activated condition
In the case of a fire that justifies extinguishing, the second fire detector triggers
within a few seconds. If the second fire detector does not trigger for a longer period
of time, you can inspect the fire location, silence the alarm horn and the buzzer and
block automatic activation of extinguishing.
Here's how to proceed, in order to block the automatic activation of extinguishing:
1. Press the "Silence Buzzer" (6) key
2. Enable operating access level 2 (access code or key)
3. Press the "Silence Re-sound Horn" (5) key
4. Press the "Mode Select" (8) key
yellow LED « Automatic blocked » (16) and « Disabled » (6) light up (fixed)
If you find the alarming fire detector and the cause, you can reset the system and
cancel the blocking of the automatic activation of extinguishing.
Here's how to proceed, in order to cancel the blocking of the automatic activation of
extinguishing:
1. Enable operating access level 2 (access code or key)
2. Press the "Reset" (8) key
yellow LED « Automatic blocked » (16) and « Disabled » (6) are no longer lit
Activated
The second fire detector in the extinguishing area has detected a fire or you have
activated extinguishing manually by pressing the Manual Release button.
-
the alarm horn becomes a pulsating tone
-
the illuminated warning panel is activated
-
the red Leds "Detector Zone 1" and "Detector Zone 2" or possibly the red Led
"Manual Release Zone 4" light up
-
the red Led "Activated" (17) changes from flashing to fixed
-
the Led « Remote transmission » (9) lights up
-
the pre-warning time starts counting down (adjustable from 0 to 60 seconds - 30
seconds by default)
-
the 4 digit display show the pre-warning time count down (XC1003-A and
XC1005-A)
A6V10257477_c_en_--
2012-06