Siemens SITRANS LVL200E Panduan Petunjuk Pengoperasian - Halaman 12

Jelajahi secara online atau unduh pdf Panduan Petunjuk Pengoperasian untuk Beralih Siemens SITRANS LVL200E. Siemens SITRANS LVL200E 40 halaman. Vibrating switches
Juga untuk Siemens SITRANS LVL200E: Buku Petunjuk (40 halaman), Panduan Petunjuk Pengoperasian (44 halaman), Panduan Petunjuk Pengoperasian (16 halaman)

Siemens SITRANS LVL200E Panduan Petunjuk Pengoperasian
Suitability for the process
conditions
Switching point
12
4

Mounting

4.1

General instructions

Make sure that all parts of the instrument coming in direct contact
with the process, especially the sensor element, process seal and
process fitting, are suitable for the existing process conditions, such
as process pressure, process temperature as well as the chemical
properties of the medium.
You can find the specifications in chapter "Technical data" and on the
nameplate.
In general, SITRANS LVL200E can be installed in any position. The
instrument only has to be mounted in such a way that the tuning fork
is at the height of the desired switching point.
The tuning fork has lateral markings (notches) that indicate the
switching point with vertical mounting. The switching point applies
to water in conjunction with the basic setting of the density switch
≥ 0.7 g/cm³ (0.025 lbs/in³). When mounting SITRANS LVL200E, make
sure that this marking is at the height of the requested switching point.
Keep in mind that the switching point of the instrument will shift if the
medium has a density other than water - water is 1 g/cm³ (0.036 lbs/
in³). For products ≤ 0.7 g/cm³ (0.025 lbs/in³) and ≥ 0.5 g/cm³
(0.018 lbs/in³) the density switch must be set to ≥ 0.5 g/cm³.
Keep in mind that foams with a density ≥ 0.45 g/cm³ (0.016 lbs/in³)
are detected by the sensor. This can lead to erroneous switchings,
particulary when the sensor is used for dry run protection.
SITRANS LVL200E - Operating Instructions
*7ML19985KY01*