Siemens VT250 Panduan Petunjuk Pengoperasian - Halaman 8

Jelajahi secara online atau unduh pdf Panduan Petunjuk Pengoperasian untuk Beralih Siemens VT250. Siemens VT250 46 halaman. 3vt switch disconnector
Juga untuk Siemens VT250: Panduan Petunjuk Instalasi (9 halaman), Panduan Petunjuk Pengoperasian (8 halaman)

Siemens VT250 Panduan Petunjuk Pengoperasian
Operating Instructions
Installation type
For the VT630 the fixed-mounted circuit breaker is the basic
version. This can be converted very easily into a plug-in version
with the aid of the appropriate mounting set. This set contains
blade contacts, a locking pin and terminal covers for the plug-in
version. See Fig. 5 for VT630 plug-in version pictures and
dimensions.
circuit breaker
(5) VT630 plug-in version
8
CAUTION
If an undervoltage release has been installed, it must be
energized, otherwise the circuit breaker cannot be closed!
After a tripping operation due to thermal overload, the circuit
breaker can only be reclosed after a cooling period of several
minutes.
6 Cross-sections for main conductors and tightening torques
7 Connection diagram for 3- and 4-pole circuit breakers
8 Toggle lever position and switching state
9 Toggle lever switching state indication
10 Shunt trip
11 Undervoltage release
12 1st auxiliary switch
13 2nd auxiliary switch
14 Alarm switch
15 Position of toggle lever
16 Auxiliary switching states
17 Alarm switching states
18 Rating under different temperatures
19 TM trip unit picture and ETU front panel
20 Range of current settings for thermal magnetic overload
tripping
21 Tripping characteristic curve
22 Protective curve of ETU
(6)
Rated current
Cross-section
mm
400 A
120 x 2
500 A
150 x 2
630 A
185 x 2
(7)
Undervoltage release conforms to IEC947-2
(8)
English
Tightening torques
2
Nm
6 ~ 10