ActronAir CL01-2G Panduan Petunjuk Instalasi - Halaman 5
Jelajahi secara online atau unduh pdf Panduan Petunjuk Instalasi untuk Panel Kontrol ActronAir CL01-2G. ActronAir CL01-2G 8 halaman. Control interface
CL01 IS CONNECTED
TO THE J9FBUS1
TERMINALS ON OCB
NOTE:
DO NOT CONNECT
SCREEN WIRE AT
WALL CONTROL
POWER
485A
WC-1
DATA CABLE:
4 CORE (2 PAIR) TWISTED PAIR
7/0.20 (AWG24) MINIMUM
SHIELDED DATA CABLE
INSTALLER TO PROVIDE
B
INCLUDED INDOOR UNIT
Description
Rev.
A
ORIGINAL
INDOOR UNIT
FOR CAY470-700T ONLY
FIELD WIRING BY INSTALLER -
CABLE MUST BE 2 CORE 7/0.30
SHIELDED TWISTED PAIR DATA CABLE
WITH SCREEN WIRE CONNECTED TO
J9FBUS1 "GND" TERMINAL ON OCB
TWISTED PAIR 1: DATA
485A TO R+/T+ TERMINAL
485B TO R-/T- TERMINAL
TWISTED PAIR 1: DATA
485A TO R+/T+ TERMINAL
485B TO R-/T- TERMINAL
TWISTED PAIR 2: POWER
POWER TO Vout TERMINAL
GND TO GND TERMINAL
OCB
2671
RL
30-03-2016
PCR
By
Date
This drawing remains the intellectual property of Actron Engineering
Pty Ltd. Reproduction, modification and/or distribution are prohibited
without written consent.
GLASS FUSE
240V AC
250V AC 10 A
POWER IN
SLOW BLOW
SIZE 5 x 20mm
N
AC250VAC/10A
FUSE1
A
IFB
ON
OFF
1 2 3 4
DIP SWITCH
FAULT
0-10V
0-10V
AUX
485
INPUT
IN
OUT
OUTPUT
OUTDOOR
AUX
COIL
COM
DI1
10V
0V
10V
0V
COM
NC
NO
A
B
SENSOR
SENSOR
1
3
1
2
CAY470-700T
Variation Code:
Base
R
PKY470-960T
6Q2-3Q2
Model No:
Description:
CM100 TRI-CAPACITY CONTROL SYSTEM WIRING DIAGRAM
WITH CL01 WALL CONTROLLER
Drawn:
MH
Date:
01-04-2015
MJH
Date:
30-03-2016
Approved:
LEGEND
I/F
IFB
OCB
TERM
WC-1
ACTRONAIR FACTORY
SUPPLIED & FITTED
I/F
Variation:
CM100 CONTROLS WITH
CL01 WALL CONTROLLER
Revision
Size:
Drawing No:
9525-4903
B
A4