Acuity Brands SensorSwitch sPODM Series Manual
Jelajahi secara online atau unduh pdf Manual untuk Beralih Acuity Brands SensorSwitch sPODM Series. Acuity Brands SensorSwitch sPODM Series 2 halaman. Sensor interface switch
SWITCHPOD
• SENSOR INTERFACE SWITCH •
MANUAL/AUTO ON • LOW VOLTAGE • PUSH-BUTTON
SPECIFICATIONS
FEATURES
Enables Standard Occupancy Sensors
to be used for Manual On Operation
Alternative Usage as Override Switch
for Auto-On Applicaitons
Single Gang Decorator Style w/
either 1 or 2 On/Off Switches
Soft-Click Push-Buttons
Programmable w/o Removing
Switch Plate
Optional Dual Manual On Operation
Optional 3-Way Operation
Optional 0-10 VDC Dimming Control
PHySICAL SPECS
SIZE
(not including ground strap)
2.74" H x 1.68" W x 1.63" D
(6.96 cm x 4.27 cm x 4.14 cm)
WEIGHT
2 oz
MOUNTING
Single Gang Switch Box or
Low Voltage Ring
COLOR
White, Ivory, Gray, Lt. Almond,
& Black
ELECTRICAL SPECS
OPERATING VOLTAGE
12-24 VAC/VDC
CURRENT
5 mA
DIMMING LOAD
Sinks < 20mA;
~40 Ballasts @ .5mA each
WIRES (all 20 AWG)
sPODM (SA): 4
sPODM 2P (2SA): 6
sPODM (SA) 3X: 6
sPODM (SA) D: 5
sPODM (SA) 3X D: 7
RECOMMENDED POWER PACK
PP20
ENVIRONMENTAL SPECS
OPERATING TEMP
14º to 160º F (-10º to 71º C)
RELATIVE HUMIDITY
20 to 90% non-condensing
OTHER
Class 2 Low Voltage
Title 24 System Device
5 Year Warranty
Assembled in the U.S.A.
ORDERING INFO
# OF SWITCHES/DEFAULT ON OPER.
Blank = 1 Switch / Auto-On
SA = 1 Switch / Manual On
2P = 2 Switches (Pole 1 Manual / Pole 2 Auto)
2P 2SA = 2 Switches (Both Poles Manual)
®
sPODM
The Push-Button SwitchPod (sPODM) Series of
low voltage wall stations interface with standard
Sensor Switch occupancy sensors and power
packs in order to implement a wide range
of single and bi-level switching applications.
These switch devices provide an elegant and
cost effective way of deploying bi-level lighting
control that meet energy and building codes
without having to source special sensors or
power packs.
Commonly required by building codes (such as
California Title 24), bi-level lighting control is
an easy and convenient method of delivering
extra energy savings without inconveniencing
the occupants. The most common bi-level
configuration requires one lighting load to be
switched on automatically when occupancy is
detected by an occupancy sensor, while a second lighting load can be turned on manually
by the occupant if desired. Both loads can then be turned off manually or via the occupancy
sensor timing out. Sensors with photocells can also be configured with SwitchPods in order to
add override off capabilities.
SwitchPods are all single gang decorator style devices available as single or dual switch units.
Versions are also available that work in 3-way applications and/or have a 0-10 VDC dimming
output. Units defaulted to dual manual-on operation are also available. For digital solutions
to bi-level lighting applications, nLight-enabled wall stations (WallPods), power packs, and
sensors are necessary.
OPERATION / WIRING INFORMATION
STANDArD (SPODM / SPODM SA)
RED
- Power (12-24 VAC/VDC)
BLACK
- Common
WHITE
- Occupancy Sensor Input
WHITE w/ BLUE STRIPE - Output to Relay
note: Default output functionality (Manual On vs.
Auto-On) is determined by model number, but
re-configurable using push-button sequence
3-WAY OPTION (3X OPTION)
YELLOW - Remote Switch I/O
YELLOW w/ BLACK STRIPE - Remote Switch I/O
DIMMING OPTION (D OPTION)
VIOLET
- 0-10 VDC Output (wire to VIOLET on
0-10 VDC dimmable ballast)
sPODM [# OF SWITCHES/DEFAULT ON OPER.] [3-WAy]* [DIMMING]* [COLOR] [TEMP/HUMIDTy]
3-WAy*
Blank = None
3X = 3-Way
OPTIONS
MulTIWAY INTERFACE (3X)
• Interfaces w/ other units for 3-way or
• Only available on single on/off version
DIMMING (D)
• Enables user control of 0-10 VDC
COlOR (must be specified)
• White, Ivory, Gray, Light Almond,
• Wall plate provided
lOW TEMP/HIGH HuMIDITY (lT)
• Device electronics are coated for
corrosion resistance
• Operates down to -40º F/C
2P OPTION (SPODM 2P / SPODM 2P 2SA)
WHITE
WHITE w/ BLUE STRIPE - Pole 1 Output to Relay
BLUE
BLUE w/ WHITE STRIPE - Pole 2 Output to Relay
note: Default output functionality (Manual On vs.
Auto-On) is determined by model number, but
re-configurable using push-button sequence
ON OFF
ON
ON OFF
ON OFF
OFF
ON OFF
DIMMING*
COLOR
Blank = None
WH = White
D = Dimming
IV = Ivory
Operation
GY = Gray
AL = Light Almond
BK = Black
*
Not available with 2 switch (2P) versions
additional configurations
dimmable ballasts
Black
- Pole 1 Occupancy Sensor Input
- Pole 2 Occupancy Sensor Input
2P BUTTONS CONTrOLS
- top two buttons always
control the Pole 1 Output
1
- bottom two buttons always
ON
ON / OFF
control the Pole 2 Output
OFF
2
ON
OFF
TEMP/HUMIDTy
Blank = Standard
LT = Low Temp