d) Turn power on, push CLS button, gate should close. If gate opens, turn power off, change motor
direction by swapping any two of three phases output of inverter.
e) Power on again. push CLS button, gate should close. If gate runs only short distance (about 2
seconds) and stop. Turn power off, change encode plug to another connector and try again.
f)
Power on again, push and hold CLS button for about 5 seconds until both OPENLED (green)
and CLSLED (Red) is solid on, release CLS button, gate will start closing at low speed.
g) Gate hit closed post/closed stopper and stop, short delay, then start opening at low speed.
i) While in this opening cycle, if push and release PED button, that current position will be saved as
pedestrian open position.
j) When gate hit opened post/opened stopper and stop, all setting is finished
k) Test gate by push buttons on board, if gate position is not right, then redo it again from step f.
5.2 MOD2: -- E-code with one limit switch: DIP2 off and DIP4 on
MOD2 – E-code with one N/O limit (either mechanical or proxy switch).
Limit Switch input as manual release spanner protection input –OPTION. Normally do not
need it. CLM --- Close Limit Switch MUST need, one limit switch work as closed and opened
limit
In this mode, gate how to stop: encoder only determine the slow down point. Gate is only
stopped by limit switch, or max. motor running time--- which is motor low speed running time,
plus 5 seconds extra. For example, if gate open take 30 seconds in learning cycle/low speed,
then max running time is 35 seconds.
Proxy switch can be mounting horizontal (like normal limit switch) or vertical.
Either in closed or opened positions, as long as moved gate without turn power off and Proxy
switch/limit switch status/state/situation has been changed, next operation will be in low
speed and automatically back to normally after two operations.
Set travel limits – (Gate travel distance setup – "learn" how long the gate)
Method B (automatic set up only). Refer MOD1---method B
5.3 MOD3: -- F-Code with two N/C limit switch: DIP2 on and DIP4 off
Mode-3 Two limit switch required N/C, proxy switch or mechanical limit switch. F-code is the
little circuit connection to inverter output and check frequency information and send to
controller.
OLM---Open Limit Switch input. CLM --- Close Limit Switch input.
In this F-code mode, gate how to stop? F-code only determine the slow down point. Gate is
only stopped by limit switch, or max. motor running time--- which is motor low speed running
time in learning cycle, plus 5 seconds extra. For example, if gate open take 30 seconds in
learning cycle/low speed, then max running time is 35 seconds
Either in closed or opened positions, as long as moved gate and limit switch status changed,
next operation will be in low speed and automatically back to normally after two operations.
Set travel limits – (Gate travel distance setup – "learn" how long the gate)
a) Mounting motor
b) Moving gate in middle position. Power up, touch limit by screw drive in open and close
direction, open limit LED and close LED will off respectively.
c) Set up limit stopper potions. When stopper touch limit and travel another 30 to 50mm, gate
should hit mechanical stopper.
d) Push Open button, gate should open. If gate close, then swap any inverter output.
P750V5.0 industrial gate motor manual
Controller Working Mode
8
OLM---Open
.