4.2 Model Select Switch
4.2.1 SYNC Delay (DIP1)
DIP1 is on: Motor 2 delay open and motor 1 delay close. DIP1 is off, there is no delay. Not apply
to Torque motor.
4.2.2 TORQUE Motor (DIP2)
DIP2 is ON, control two boom gate torque motors. OPN open both boom gates, while PED only
open boom gate driven by motor1. DIP2 is OFF, it control standard 240V AC motors.
4.2.3 WARN (DIP3)
DIP3 is ON, about 3 seconds audio warning before gate starts. DIP3 is off, no this function.
4.2.4 M2ST (DIP4)
DIP4 is on, Motor 2's out changes to light out. OP2 out is continually, CL2 out is flash at about
1Hz either open or close cycle.
4.2.5 LOCK (DIP5)
DIP5 on, the lock output is presence. The lock relay will be on if the gate is in opening, closing
cycle. DIP5 is off; lock output is 0.8 seconds pulse at the start of each open and close cycle.
4.2.6 PEOP (DIP6)
DIP6 is ON, the PE beam will work on the open cycle and close cycle. DIP6 is off; the PE beam
will work only in close cycle.
4.2.7 NOLS (DIP7)
DIP7 is ON, the limit inputs change to N/O, and DIP7 is off, the limit inputs are N/C
4.2.8 Security close (DIP8)
DIP8 is on and P.E input is active while the gate is opening, if the PE clear, the gate controller
stops gate and begin to close the gate even the gate is not fully opened. If the PE active again, gate
will just stop, but not reopen. If DIP8 is set to off, there is no this function.
4.2.9 PE trig close (DIP9)
If DIP9 is set to ON, after gate opened, the gate will auto close after P.E beams trigged and clear.
If the P.E beams trig again, the gate will reopen as long as the P.E input is keep active until gate
fully opened. If the PE is clear, the gate will only open another 2 seconds, then after PE close
delay time will close again. DIP8 is prior to DIP9.
4.2.10 Auto CLS (DIP10)
If DIP10 is on, the gate will auto close after standard auto closed time (30 seconds). If DIP10 is
off, the gate will stay opened if no other input to the controller. DIP9 is prior to DIP10
Digiway Pty Ltd
CONTROL INPUIT AND BUTTON
ON= Delay
OFF= No Delay
ON=TORQUE
OFF= 240VAC Motors
ON= Warn
ON= M2 LGT out OFF= Motor out
ON= presence
OFF= pulse
ON= PEOP
OFF=Close only
ON= N/O limit
ON=SEC CLS
OFF=NO SEC CLS
ON=PE CLS
OFF=NO PE CLS (2.0sec)
ON=AUTO CLS
OFF=NO AUTO CLS (30sec))
7
OFF= No Warn
OFF=N/C limit