4-0 DIP Switch and Jumper
Identification and Configuration
4-3 Input Wiring - cont'd
Sensor Input Type
•
Dry Contact input.
•
Pulsed input.
•
Pulse input used with a 2-wire sensor powered by its own
power source – this input supports a maximum input
frequency of 1Hz (500ms minimum ON/OFF). Connect the
pulse input according to the figure for a pulse meter that can
pull-down a +5VDC supply with a 10KΩ pull-up resistor
(Internal supply type).
•
RTD input (for example, 1000Ω).
•
Thermistor Input (for example, 10kΩ type II and III).
•
Resistive input, maximum 350kΩ (for example, use with
10kΩ and 100kΩ potentiometers).
•
0 to 20mA input used with a 2-wire, 0 to 20mA sensor
powered by the control-ler's internal 18VDC power supply.
•
See DIP Switch and Jumper Identification and Configuration
on page 5 for more information about how to set the DIP
Switch.
•
0 to 20mA input used with a 2-wire, 0 to 20mA sensor
powered by an external 24 AC/DC power supply.
•
See DIP Switch and Jumper Identification and Configuration
on page 5 for more information about how to set the DIP
Switch.
•
0 to 20mA input used with a 3-wire, 0 to 20mA sensor
powered by an external 24 AC/DC power supply.
•
See DIP Switch and Jumper Identification and Configuration
on page 5 for more information about how to set the DIP
Switch.
•
0 to 20mA input used with a sensor powered by its own
power source.
•
See DIP Switch and Jumper Identification and Configuration
on page 5 for more information about how to set the DIP
Switch.
•
Voltage input used with a 3-wire 0 to 10VDC or 0 to 5VDC
sensor powered by an external 24 AC/DC power supply.
•
Voltage input used with a 0 to 10VDC or 0 to 5VDC sensor
powered by its own power source.
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com © 2019 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/07/2019
- cont'd
8UI6UOHOA
Modules' Input
Designation
•
UIx
•
UIx
•
UIx
•
UIx
•
UIx
•
UIx
•
UIx
•
UIx
•
UIx
•
UIx
Input Connection Diagram
7 of 14