ECI LiteWizard Panduan Instalasi - Halaman 8

Jelajahi secara online atau unduh pdf Panduan Instalasi untuk Panel Kontrol ECI LiteWizard. ECI LiteWizard 9 halaman.

INPUT

7.4.3 Timer Adjustments

There is one potentiometer (TIMER 1 and TIMER 2) associated with each relay (RELAY 1 and RELAY
2). Use these to adjust the time delay from the time all inputs are valid to power being turned off.

7.4.4 TEST button

Pressing the test button lights the TEST LED. This will shorten the delay times for the RELAYS to 10%
to allow for easy testing before closing up. Pressing the TEST button a second time will disable test
mode.

8 Installation

Be sure power is disconnected before starting installation
Configure all inputs for proper voltage
Set the OPTION switches to the ON position for each input used. NOTE: switch 6 must always
be ON
Turn TIMER 1 and 2 potentiometers fully counter-clockwise.
Connect Cab lights and FAN power through desired relay output connections
Connect AC power to pin 34 and 35.
Apply power to unit
o Some input LEDs may light.

9 Testing

NOTE: Before testing be sure that input combination for turning off lights and fan is
not valid; i.e. at least one of the inputs must be invalid or off and, if used, input 6
must be invalid or off.
Press the TEST button
o The TEST LED should light
Put the inputs into the combination that should start the timer.
LiteWizard™ Installation Manual
TERMINAL PINS
1
2
3
4
5
9,10
6
11,12
Electronic Controls, Inc.
7073 North Atlantic Ave. Cape Canaveral, FL 32920
800-633-9788
www.eciamerica.com
OPTION SWITCH
1, 2
3,4
5,6
7,8
1
2
3
4
5
6
P a g e
| 8