14
Residual overvoltage relay module SPCU 1C6
See "Technical data" in the document 1MRS 750509-MUM EN for the relay module.
Two-stage undervoltage relay module SPCU 3C15
See "Technical data" in the document 1MRS 750588-MUM EN for the relay module.
Data communication
Transmission mode
Coding
Data transfer rate, selectable
Optical bus connection module powered from
the host relay
- for plastic-core cables
- for glass-fibre cables
Optical bus connection module powered from
the host relay or from an external power source
- for plastic-core cables
- for glass-fibre cables
Test voltages *)
Dielectric test voltage according to IEC 255-5
Impulse test voltage according to IEC 255-5
Insulation resistance according to IEC 255-5
Disturbance tests *)
High-frequency (1 Mhz) disturbance test
according to IEC 255-22-1
- common mode
- differential mode
Electrostatic discharge test according
to IEC 255-22-2 and IEC 801-2, class III
- air discharge
- contact discharge
Fast transients according to IEC 255-22-4,
class III and IEC 801-4, level IV
- power supply inputs
- other inputs
Rf electromagnetic field test according to
IEC 1000-4-3 and ENV 50140, f = 80...1000 Mhz
Conducted rf disturbance test according to
ENV 50141 and IEC 1000-4-6, f = 150 kHz...80 Mhz
Fibre-optic serial bus
ASCII
300, 1200, 2400, 4800 or 9600 Bd
SPA-ZC 21 BB
SPA-ZC 21 MM
SPA-ZC 17 BB
SPA-ZC 17 MM
2 kV, 50 Hz, 1 min
5 kV, 1.2/50 µs, 0.5 J
>100 MΩ, 500 V dc
2.5 kV
1.0 kV
8 kV
6 kV
4 kV, 5/50 ns
2 kV, 5/50 ns
10 V/m
10 V