CHECK function
This function is normally disabled and can be
OFF).
This function controls the electrical connections made
the electrical connections made during installation, switching on the
compressor, the fan and the 4-ways valve; the procedure must be done
inside the tank is below 30 °C.
The CHECK procedure takes about 8 minutes during which the progress symbols
procedure takes about 8 minutes during which the progress symbols (triangles in the
bottom of the display) flashes on the display.
flashes on the display.
If at the end of the procedure the result is "OK", the electrical connections were made
If displayed "KO ", recheck the electrical connections
heck the electrical connections between indoor and external unit paying
attention to the numbers indicated on the terminals. Check
attention to the numbers indicated on the terminals. Check sensors cable.
To stop this procedure press "mode ".
CHARGE function
This function is normally disabled and can be
OFF).
This function allows to make a refrigerant gas
The CHARGE procedure lasts for 30 minutes, then it stops
electrical resistance (1200 W) could switch on
water.
If an error occurs while charge is running, the function shall be
If an error occurs while charge is running, the function shall be paused or stopped and the error
code displayed.
The charge present in the external unit is sufficient for a connection to the internal unit up to 6m
The charge present in the external unit is sufficient for a connection to the internal unit up to 6m
The charge present in the external unit is sufficient for a connection to the internal unit up to 6m
long.
Use an electronic balance to measure the quantity of gas
Use an electronic balance to measure the quantity of gas added by the weight of the gas bottle.
RESET function
This function can be enabled via installer menu (P10
enabled via installer menu (P10 Parameter).
The RESET function restores all the factory default settings:
Parameter
AUTO MODE
BOOST MODE
PRE-SET TEMPERATURE
P1
MAX. TEMPERATURE SETTABLE WITH THE
TEMPERATURE SETTABLE WITH THE HEATING ELEMENT
P2
MINIMUM SETTABLE TEMPERATURE
MINIMUM SETTABLE TEMPERATURE
P3
MAX. TEMPERATURE SETTABLE WITH THE HEAT PUMP
TEMPERATURE SETTABLE WITH THE HEAT PUMP
P4
GREEN MODE
P5
ANTI-LEGIONNAIRE'S DISEASE PROTECTION
LEGIONNAIRE'S DISEASE PROTECTION
P6
VOYAGE MODE
P7
DEFROST (active defrost activation)
P8
HC-HP (off peak rate operation mode)
P9
TIME_W (no. of accepted hours of powering)
TIME_W (no. of accepted hours of powering)
P11
PROGRAM MODE (P1, P2, P1+P2)
PROGRAM MODE (P1, P2, P1+P2)
PROGRAM P1 TEMPERATURE PRESET
PROGRAM P1 TEMPERATURE PRESET
PROGRAM P1 TIME PRESET
PROGRAM P2 TEMPERATURE PRESET
PROGRAM P2 TIME PRESET
can be enabled via installer menu (C1 Parameter: default =
; the procedure must be done if the water temperature
"OK", the electrical connections were made properly.
can be enabled via installer menu (C2 Parameter: default =
gas addition inverting the thermodynamic cycle.
30 minutes, then it stops automatically. During this time the
on, so it's mandatory to use it with the tank full of
the factory default settings:
activation)
rate operation mode)
TEMPERATURE PRESET
: default =
if the water temperature
: default =
28
Factory default setting
ACTIVATED
ACTIVATED
55°C
65°C
50°C
55°C
DEACTIVATED
DEACTIVATED
DEACTIVATED
ACTIVATED
DEACTIVATED
8h
DEACTIVATED
55°C
06:00
55°C
18:00