ABB ACS850 series Panduan Instalasi Cepat - Halaman 6

Jelajahi secara online atau unduh pdf Panduan Instalasi Cepat untuk Unit Kontrol ABB ACS850 series. ABB ACS850 series 16 halaman. Drive modules, 55...160 kw, 75...200 hp

ABB ACS850 series Panduan Instalasi Cepat
6

Installing the control cables

Default I/O connection diagram
Notes:
[Default setting with ACS850 standard
control program (Factory macro).
*Total maximum current: 200 mA
The wiring shown is for demonstrative
purposes only.
For jumper settings, see text.
Wire sizes and tightening torques:
XPOW, XRO1, XRO2, XRO3, XD24:
2
0.5 ... 2.5 mm
(24...12 AWG). Torque:
0.5 N·m (5 lbf·in)
XDI, XDIO, XAI, XAO, XD2D, XSTO:
2
0.5 ... 1.5 mm
(28...14 AWG). Torque:
0.3 N·m (3 lbf·in)
Order of terminal headers and
jumpers
XPOW
2
(2-pole, 2.5 mm
)
XRO1
2
(3-pole, 2.5 mm
)
XRO2
2
(3-pole, 2.5 mm
)
XRO3
2
(3-pole, 2.5 mm
)
XD24
2
(4-pole, 2.5 mm
)
DI/DIO grounding selection
XDI
2
(7-pole, 1.5 mm
)
XDIO
2
(2-pole, 1.5 mm
)
XAI
2
(7-pole, 1.5 mm
)
AI1, AI2
XAO
2
(4-pole, 1.5 mm
)
T
XD2D
2
(3-pole, 1.5 mm
)
XSTO (orange)
2
(4-pole, 1.5 mm
)
Quick installation guide – ACS850-04
External power input
24 V DC, 1.6 A
Relay output RO1 [Ready]
250 V AC / 30 V DC
2 A
Relay output RO2 [Modulating]
250 V AC / 30 V DC
2 A
Relay output RO3 [Fault(-1)]
250 V AC / 30 V DC
2 A
+24 V DC*
Digital input ground
+24 V DC*
Digital input/output ground
Ground selection jumper
Digital input DI1 [Stop/Start]
Digital input DI2
Digital input DI3 [Reset]
Digital input DI4
Digital input DI5
Digital input DI6 or thermistor input
Start interlock (0 = Stop)
Digital input/output DIO1 [Output: Ready]
Digital input/output DIO2 [Output: Running]
Reference voltage (+)
Reference voltage (–)
Ground
Analog input AI1 (Current or voltage, selectable by jumper AI1) [Speed
reference 1]
Analog input AI2 (Current or voltage, selectable by jumper AI2)
AI1 current/voltage selection jumper
AI2 current/voltage selection jumper
Analog output AO1 [Current %]
Analog output AO2 [Speed %]
Drive-to-drive link termination jumper
Drive-to-drive link.
Safe Torque Off. Both circuits must be closed for the drive to start.
Control panel connection
Memory unit connection
XPOW
+24VI
1
GND
2
XRO1, XRO2, XRO3
NO
1
COM
2
NC
3
NO
4
COM
5
NC
6
NO
7
COM
8
NC
9
XD24
+24VD
1
DIGND
2
+24VD
3
DIOGND
4
AI1
XDI
DI1
1
DI2
2
DI3
3
DI4
4
DI5
5
DI6
6
DIIL
A
XDIO
DIO1
1
DIO2
2
XAI
+VREF
1
-VREF
2
AGND
3
AI1+
4
AI1-
5
AI2+
6
AI2-
7
AI1
AI2
XAO
AO1+
1
AO1-
2
AO2+
3
AO2-
4
XD2D
T
B
1
A
2
BGND
3
XSTO
OUT1
1
OUT2
2
IN1
3
IN2
4