Whirlpool 8527902 Panduan Petunjuk Instalasi - Halaman 8

Jelajahi secara online atau unduh pdf Panduan Petunjuk Instalasi untuk Pengering Whirlpool 8527902. Whirlpool 8527902 25 halaman. Commercial electronic dryer

Whirlpool 8527902 Panduan Petunjuk Instalasi
6. Make e ectr ca connection,
Power supply cord
Direct wire
This dryer is manufactured
with the
cabinet-ground
conductor
connected
to the NEUTRAL(center) of
the widng harness at the terminal
block. If local codes
do NOT permit
this type of connection,
use "Four-
wire connection"
instructions.
For a grounded,
cord-connected
appliance
--
GROUNDING
INSTRUCTIONS:
This appliance
must be grounded,
In
the event
of malfunction
or
breakdown,
grounding
will reduce
the risk of electric
shock by providing
a path of least resistance
for electric
current,
If using a power supply cord, the plug
must be plugged
into an appropriate
outlet
that is properly
installed
and
grounded
in accordance
with all
local codes
and ordinances,
WARNING - Improper
connection
of
the equipment-grounding
conductor
can result in a risk of electric
shock,
Check with a qualified
electrician
or
serviceman
if you are in doubt
as to
whether
the appliance
is properly
grounded,
Do not modify
the plug
provided
with the appliance
- if it will
not fit the outlet,
have a proper
outlet
installed
by a qualified
electrician,
For a permanently
connected
appliance
--
GROUNDING
INSTRUCTIONS:
This appliance
must be connected
to
a grounded
metal, permanent
wiring
system; or an equipment-grounding
conductor
must be run with the
circuit conductors
and connected
to
the equipment-grounding
terminal
or
lead on the appliance,
Use a new UL-approved
power supply
cord rated 24D-volt min., 30 amperes
and marked for use with a clothes
dryer.
Fire Hazard
Use a new UL approved 30
ampere power supply cord.
Use a UL approved strain relief.
Disconnect power before making
electrical connections.
Connect neutral wire (white or
center wire) to center terminal
(silver).
Ground wire (green or bare wire)
must be connected to green
ground connector.
Connect remaining 2 supply
wires to remaining 2 terminals
(gold).
Securely tighten all electrical
connections.
Failure to do so can result in
death, fire, or electrical shock.
Fire Hazard
Use 10 gauge solid copper wire.
Use a UL approved strain relief.
Disconnect power before making
electrical connections.
Connect neutral wire (white or
center wire) to center terminal
(silver).
Ground wire (green or bare wire)
must be connected to green
ground connector.
Connect remaining 2 supply
wires to remaining 2 terminals
(gold).
Securely tighten all electrical
connections.
Failure to do so can result in
death, fire, or electrical shock.
I.
Disconnect the power supply.
external ground
_/,_ductor
screw
tab r._J
_-i
hold-
i/down
_
screw
2.
Remove
hold-down
screw
and terminal
block cover,
strain
_dryer
relief
//_._
\cabinet
clamp
I_._.L _
sections_
/
--
_
strain relief
,3. Assemble
screws
3/4" U,L,-listed strain relief
(U,L, marking
on strain relief) into the
hole below terminal
block opening,
Tighten strain relief screws just enough
to hold the two clamp
sections
together,
Install power supply
cord/cable
through
the strain relief,
Complete
installation following
instructions for your type of
connection:
• Four-wire (recommended
method)
• Three-wire (if tour-wire
is not
available)
Page 8