Installation Dimensions
12"
(30.5 cm)
10
" (26.7 cm)
12"
(30.5 cm)
Side
cabinet
36"
(91.4 cm)
min.
Centerline

Venting Requirements

Vent system must terminate to the outside, except for non-
vented (recirculating) installations.
Do not terminate the vent system in an attic or other enclosed
area.
Do not use 4" (10.2 cm) laundry-type wall caps.
Use metal vent only. Rigid metal vent is recommended. Do
not use plastic or metal foil vent.
The vent system must have a damper. If the roof or wall cap
has a damper, do not use the damper supplied with the range
hood.
For the most efficient and quiet operation:
Use a straight run or as few elbows as possible.
Use no more than three 90° elbows.
Make sure there is a minimum of 24" (61 cm) of straight vent
between the elbows if more than 1 elbow is used.
Do not install 2 elbows together.
Use clamps to seal all joints in the vent system.
Use caulking to seal exterior wall or roof opening around the
cap.
The size of the vent should be uniform.
Cold weather installations
An additional back draft damper should be installed to minimize
backward cold air flow. A nonmetallic thermal break should be
installed to minimize conduction of outside temperatures as part
of the vent system. The damper should be on the cold air side of
the thermal break.
The break should be as close as possible to where the vent
system enters the heated portion of the house.
Makeup air
Local building codes may require the use of makeup air systems
when using ventilation systems greater than specified CFM of air
movement.
2" (5.1 cm) min.
Vent and power
supply cable entry
location
21"
(53.3 cm)
min.
Side
cabinet
30" (76.2 cm) min.
bottom of canopy to
cooking surface
The specified CFM varies from locale to locale. Consult your
HVAC professional for specific requirements in your area.
Venting Methods
This canopy hood is factory set for venting through the roof or
wall.
An 8" (20.3 cm) round vent system is needed for installation (not
included). The hood exhaust opening is 8" (20.3 cm) round.
NOTE: Flexible vent is not recommended. Flexible vent creates
back pressure and air turbulence that greatly reduce
performance.
Vent system can terminate either through the roof or wall. To vent
through a wall, a 90° elbow is needed.
Rear discharge
A 90° elbow may be installed immediately above the hood.
For non-vented (recirculating) installations
If it is not possible to vent cooking fumes and vapors to the
outside, the hood can be used in the non-vented (recirculating)
version, fitting an activated carbon filter and the deflector. Fumes
and vapors are recycled through the top grille.
Roof Venting
Wall Venting
A
B
B
A. Roof cap
A. Wall cap
B. 8" (20.3 cm)
B. 8" (20.3 cm)
round vent
round vent
Calculating Vent System Length
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
Vent piece
8" (20.3 cm) round
45° elbow
2.5 ft
(0.8 m)
90° elbow
5.0 ft
(1.5 m)
Maximum equivalent vent length is 50 ft (15.2 m).
Non-vented
(recirculating)
A
A
B
A. Deflector
B. 8" (20.3 cm)
round vent