QUICK USER GUIDE FOR 1, 2 & 4 ZONE FIRE PANELS
INDICATORS
COLOUR
COMMON FAULT
Yellow
COMMON FIRE
Red
ZONES 1-4 FAULT
Yellow
ZONES 1-4 FIRE
Red
SUPPLY
Green
SUPPLY FAULT
Yellow
ALARM FAULT/
Yellow
DISABLED
DISABLED
Yellow
TEST
Yellow
SYSTEM FAULT
Yellow
ALARM SILENCED
Yellow
EARTH FAULT
Yellow
Document EN02/08.02
INDICATION
On when a fault condition has occurred, or if
no other fault Led is on, this indicates 24v
auxiliary fuse failure.
On when a FIRE condition has occurred or
EVACUATE has been operated.
Flashes if a detector is removed from its base,
or an open/short circuit zone wiring fault.
Illuminated when a zone is disabled and
flashes when in walktest.
Illuminated during a FIRE condition in this
zone. Flashes when a device is being tested
during walktest.
Illuminated while power is being supplied to
the panel.
Flashes during a mains or battery supply
failure.
Flashes when a fault on the sounder wiring
occurs. Illuminated if alarm lines are disabled.
Illuminated when Zones and/or alarm are
disabled. The specific zone or alarm fault led
will also be lit.
Illuminated when Walktest function selected.
Illuminated if the panel has malfunctioned and
an attempt to reset the system automatically
has been made. Flashes if an error in the
system software has been detected – Requires
attention.
Illuminated if the sounders on the alarm
circuits during a fire/evacuation condition
have been switched off or silenced.
Will flash if a fault occurs with the earthing.
FIRE
FIRE
FIRE
FIRE
tec
tec
EN54
EN54
EN54
EN54
FTEN1, FTEN2, & FTEN4
1, 2 & 4 ZONE
FIRE DETECTION AND
ALARM CONTROL PANELS
INSTALLATION INSTRUCTIONS
USER GUIDE
LOG BOOK