a.
Apply a soapy water solution to the cylinder valve connection, end of line adapter connection, and the pressure gauge connection.
b.
Observe for bubble leaks.
c.
After approximately 30 minutes, verify the pressure gauge reading. Any decrease in pressure is an indication of a leak.
d.
If the system is determined to contain a leak, verify the installation procedures were properly followed for all fittings and accessories.
11. After confirming that there is no leakage within the detection tubing, SLOWLY rotate the ball valve lever counterclockwise, to the "ON"
position.

4 SERVICE AND MAINTENANCE

4.1 General

A regular program of systematic maintenance must be established for continuous, proper operation of all Dual Pressure Switch Modules, and to avoid
violating the warranty. A periodic maintenance schedule must be followed, and an inspection log maintained for ready reference. As a minimum, the
log must record: (1) inspection interval, (2) inspection procedure performed, (3) maintenance performed, if any, as a result of inspection, and (4) name
of inspector performing task. For any deficiencies that are found, appropriate corrective actions shall be taken immediately. Inspections should be
taken on a weekly, monthly, semi-annual basis according to the connected Firetrace Suppression unit's manual.
1.
Make a general visual inspection of the unit(s) for damaged or missing parts.
2.
Ensure access to hazard areas and cylinders are unobstructed and that there are no obstructions to the operation of the equipment.
3.
Inspect detection tubing in hazard area for abrasion, distortion, cuts, or dirt accumulation, and that there are no obstructions preventing
tubing from sensing a fire should one occur.
4.
The Pressure Gauge(s) are in the operable range.
5.
Neither the Protected Equipment nor the Hazard has been replaced, modified, or relocated.
6.
Ensure that the proper electrical connections are not damaged, missing, or modified.

4.2 Post Discharge, System Recharge, and Return to Service

An authorized Firetrace distributor must be consulted after a system has discharged. The units must be removed and recharged. To remove the
connected Firetrace Suppression unit(s) please refer to that unit's manual to return to service.