3 INSTALLATION

The Dual Pressure Switch Module is an easy addition to any Firetrace fire suppression system installation. There are only a few simple steps to
complete prior to mounting the box in its desired location and connecting it to the detection tubing network.
1.
Open the pressure switch module to gain access to the configuration panel
2.
Set the toggle switches to the specified position based on the configuration required for the installation
3.
Close the pressure switch module
4.
Secure the Dual Pressure Switch Module in place
5.
Wire the pressure switch module using the supplied cable harness
6.
Insert tubing into the slip-on fitting to connect the module to the detection network
7.
Pressurize the Firetrace detection tubing.
The rest of the installation of the Firetrace fire suppression systems should follow the instructions called out in the specific DIOM of the system being
installed. Reference the following sections for more detail on each of the steps outlined above.

3.1 Opening the Module

3.1.1 With Bypass Key Switch

Reference the number callouts in Figure 6 above for the process below
1.
Remove pressure gauge (1) from integrated end-of-line adapter (4)
2.
Remove retaining nut (2) from integrated end-of-line adapter (4)
3.
Remove bonded washer (3) from integrated end-of-line adapter (4)
4.
Unscrew the four screws (5) in the corner of the box
5.
Remove cover
DIOM 800095-A
5
4
Figure 6 – Exploded View | with Bypass
4
3
2
1
7/22/2022