Caleffi solar 252219HP Petunjuk Pemasangan, Komisioning, dan Servis - Halaman 2
Jelajahi secara online atau unduh pdf Petunjuk Pemasangan, Komisioning, dan Servis untuk Unit Kontrol Caleffi solar 252219HP. Caleffi solar 252219HP 12 halaman. Tempering valve for solar and instantaneous applications
Technical data
Materials: - valve body:
- regulating spindle:
- internal shutter:
- sealing elements:
- cap:
Temperature adjustment range:
Temperature set:
Temperature control:
Minimum cold inlet temperature:
Maximum cold inlet temperature:
Minimum hot inlet temperature:
Maximum hot inlet temperature:
Maximum working pressure (static):
Maximum working pressure (dynamic):
Minimum working pressure (dynamic):
Maximum unbalanced dynamic supply (hot/cold or cold/hot):
Minimum temperature differential between hot water inlet
and mixed water outlet to ensure thermal shutoff function:
Minimum temperature differential between mixed water outlet
and cold water inlet to ensure stable operation:
Minimum flow rate for stable operation:
Dimensions
B
*
Only for 252219HP
35–50°C (55°C only under supervision and not within
Must be commissioned on site to achieve desired temperature
C
B
AS 4032.2
C of C 02466
A
2
DZR alloy EN 12165 CW602N
DZR alloy EN 12165 CW602N
requirements of AS 3500 and AS 4032.2)
Code 252212HP 252219HP
A
Ø 15
B
62,5
C
125
D
91
E
48,5
F
42,5
PPO
EPDM
ABS
±3°C
5°C
30°C
55°C
100°C
1400 kPa
500 kPa
20 kPa
6:1
10°C
5°C
4 l/min
Ø 20
69
138
126,5
84
42,5